TEXAS WASTEWATER CLASS C EXAM
TEST BANK | ALL QUESTIONS AND
CORRECT ANSWERS | ALREADY GRADED
A+ | VERIFIED ANSWERS | LATEST
VERSION Questions and Correct Answers/
Latest Update / Already Graded
The Activated Sludge Process:
A. requires preaeration
B. requires Activated Carbon
C. is an aerobic biological process.
D. Usually precedes primary sedimentation.
E. Requires 50% by volume old sludge to work effectively.
Ans: C. Is an Aerobic biological process
A complete mix activated sludge plant has a fast settling sludge and
high amounts of pin floc leaving the clarifier. One way to correct this
problem is to :
A. Increase the RAS Flow
All rights reserved © 2025/ 2026 |
, Page |2
B. Reduce Wasting Rates
C. Increase dissolved oxygen levels.
D. Increase the F/M ratio by wasting more
E. Increase the sludge age by wasting less.
Ans: D. Increase the F/M Ratio by Wasting More
Which of the following flow rates should be measured if the operator is
to control plant properly?
A. Aeration rate or resulting dissolved oxygen level.
B. Influent or effluent.
C. return sludge
D. waste sludge
E. all the above
Ans: E. all the above
During start up your aeration tank produces excessive amounts of
billowing white foam. This can be corrected by:
A. Doing nothing, it will go away in a few hours
All rights reserved © 2025/ 2026 |
, Page |3
B. Increasing the sludge wasting rate
C. Seeding the process with sufficient good quality sludge
D. Spraying water on the foam until it is gone
E. Taking a weeks vacation
Ans: C. Seeding the process with sufficient good quality sludge
In solving an operational problem at a treatment plant:
A. there is almost always a good technical solution. It may require
considerable experience and time to learn whaat it is.
B. Human errors have to be corrected since the operator is at fault.
C. don't let the laboratory personnel influence you're judgement as to
what the best solution is.
D. standard textbooks in sanitary engineering are the best source of
information.
E. It is best to do nothing until the TNRCCC sends a violation notice.
Ans: A. there is almost always a good technical solution. It may
require considerable experience and time to learn whaat it is.
When the return sludge rate is too low, what happens?
All rights reserved © 2025/ 2026 |