sprinkler test COMPREHENSIVE QUESTIONS AND
VERIFIED SOLUTIONS
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - ✔✔OWNER RECORDS OF ALL
INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN.
OF __________ YEARS. - ✔✔3 THE BUILDING OWNER SHALL ASSIGN A(N)
____________ TO COMPLY WITH REQUIREMENTS. - ✔✔IMPAIRMENT
COORDINATOR REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE
THAN ________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM
SERVICE. - ✔✔1 SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S)
ARE CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS. - ✔✔1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS
RETURNED TO SERVICE WITHIN ______ HOURS. - ✔✔8 FOR UNPLANNED
REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY
REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. - ✔✔OWNER
OF THE BUILDING IF A MINOR DEFECT IS OBSERVED, IT SHALL BE
CORRECTED WITHIN _________ DAYS OR IT WILL BE CONSIDERED AN
IMPAIRMENT. - ✔✔30 WHAT DOES "OOS" STAND FOR? - ✔✔OUT OF
SERVICE OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT
FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND
CENTER - ✔✔TAGS A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN
CONTROL VALVE AND ANY SECTIONAL VALVES. - ✔✔MASTER FIRE
SUPPRESSION PIPING CONTRACTOR __________ SHALL BE POSTED ON THE
TAG INDICATING BOTH STATIC AND FLOW PRESSURES BEFORE AND
AFTER. - ✔✔DRAIN TEST RESULTS GREEN TAGS INDICATE THAT __________.
- ✔✔NO IMPAIRMENT WAS FOUND GREEN TAGS WILL BE PLACED ON THE
____________. - ✔✔MAIN CONTROL VALVE SYSTEMS PARTIALLY OR FULLY
OUT OF SERVICE SHALL HAVE A ____________ TAG PLACED ON THE MAIN
CONTROL VALVE. - ✔✔RED A _________ DISC OF 8-9 INCHES SHALL BE
PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF
SERVICE. - ✔✔WHITE A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE.
- ✔✔BLUE THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________
, CARRIER, CENTRAL STATION AND OCCUPANTS. - ✔✔INSURANCE PRIOR TO
RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - ✔✔IMPAIRMENT
COORDINATOR GLYCERIN NOT GREATER THAN _________ PERCENT OR
GLYCOL NOT GREATHER THAN ________ PERCENT SHALL BE USED TO
PROTECT FROM FREEZING. - ✔✔50, 40 THE COF NUMBER AND SIGNATURE
OF COF HOLDER SHALL BE POSTED NEAR THE ____________. - ✔✔MAIN
CONTROL VALVE __________ SHALL BE READILY AVAILABLE TO ANY
REPRESENTATIVE OF THE FIRE DEPT. THESE ARE TO BE MAINTAINED ON
SITE FOR 3 YEARS. - ✔✔RECORDS FAILURE TO MAKE INSPECTIONS MAY
RESULT IN __________ OF THE COF AND COURT PROCEEDINGS. -
✔✔REVOCATION THE COF HOLDER MAY INSPECT, TEST, AND PERFORM
ROUTINE MX IF THEY HOLD THE FOLLOWING CERTS: - ✔✔REFRIGERATION
OPERATING ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS
HIGH PRESSURE OPERATING ENGINEER. A ________ CAN INSPECT,
MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND SPRINKLER
SYSTEMS. - ✔✔MASTER FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS. - ✔✔30 ABOUT
______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN
SPRINKLERS ARE INSTALLED. - ✔✔96 WET PIPE SYSTEMS HAVE WATER AT
A MINIMUM TEMP. OF _______ TO PREVENT THE SYSTEM FROM FREEZING.
- ✔✔40 FAHRENHEIT __________ VALVES ARE NO LONGER PERMITTED TO
BE INSTALLED. - ✔✔COLD WEATHER ________ SYSTEMS ARE INSTALLED
WHERE A WET PIPE SYSTEM CANNOT BE HEATED TO PREVENT FREEZING.
- ✔✔DRY PIPE THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE
TO OPEN. - ✔✔AIR PRESSURE IN BUILDINGS WHERE LIFE HAZARD IS HIGH
(SCHOOLS, HOSPITALS) THE ALARM IS TRANSMITTED DIRECTLY TO THE
_________. - ✔✔FIRE DEPARTMENT DRY PIPE VALVES ARE OF A ______
DESIGN. - ✔✔CLAPPER DRY PIPE VALVES ARE USUALLY SET AT ________ PSI
ABOVE THE NORMAL TRIP LEVEL. - ✔✔15-20 AN ACCELERATOR AND
EXHAUSTER ARE USED TO _______THE TIME TO ALLOW WATER INTO THE
SYSTEM. - ✔✔REDUCE BOTH ACCLERATOR AND EXHAUSTER ARE
ACTIVATED WHEN A DROP OF _______ PSI IS DETECTED IN THE SYSTEM. -
✔✔2 IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE
SPRINKLER HEADS. - ✔✔PREACTION VALVE PREACTION SYSTEM ALARMS
ARE GIVEN AS SOON AS THE _________ IS OPENED. - ✔✔VALVE THREE