Michigan Journeyman test
Questions With Complete
Solutions
1. What is the minimum size copper grounding electrode conductor required for a
200-amp residential service?


A. No. 8 AWG
B. No. 4 AWG
C. No. 6 AWG
D. No. 2 AWG
✅ Answer: C. No. 6 AWG
Explanation: NEC 250.66 — A 200A service requires a minimum No. 6 AWG copper
grounding electrode conductor when connected to a ground rod.


2. What is the maximum number of conductors allowed in a ¾-inch EMT containing
#12 THHN wires before derating must be applied?


A. 6
B. 9
C. 10
D. 16
✅ Answer: C. 10
Explanation: NEC Chapter 9, Table 1 and Table 5 — More than 3 current-carrying
conductors require derating.


3. What is the standard voltage drop recommendation for branch circuits?


A. 3%
B. 5%
C. 2%

,D. 10%
✅ Answer: A. 3%
Explanation: NEC Informational Note — Recommended maximum 3% voltage drop
on branch circuits, 5% total on feeders and branch combined.


4. Minimum burial depth for PVC conduit under a residential driveway is:


A. 6 inches
B. 12 inches
C. 18 inches
D. 24 inches
✅ Answer: D. 24 inches
Explanation: NEC Table 300.5 — PVC under driveways requires 24" cover.


5. The minimum working space in front of a 480V panelboard is:


A. 2 feet
B. 3 feet
C. 3.5 feet
D. 4 feet
✅ Answer: B. 3 feet
Explanation: NEC 110.26(A)(1) — Minimum depth of working space for 0–600V
equipment is 3 ft.


6. What color insulation is required for the grounded conductor in a 120/240V
single-phase system?


A. Green
B. White or gray
C. Red
D. Black
✅ Answer: B. White or gray

,Explanation: NEC 200.6 — Grounded conductors must be white or gray.


7. Receptacles in bathrooms must be protected by:


A. AFCI only
B. GFCI only
C. Both AFCI and GFCI
D. No protection required
✅ Answer: B. GFCI only
Explanation: NEC 210.8(A)(1) — Bathrooms require GFCI protection.


8. What is the maximum overcurrent device for #12 copper wire?


A. 15 amps
B. 20 amps
C. 25 amps
D. 30 amps
✅ Answer: B. 20 amps
Explanation: NEC 240.4(D)(5) — #12 AWG copper is limited to 20A maximum.


9. When installing NM-B cable in an attic, how far must it be kept from the edge of a
scuttle hole or attic entry?


A. 3 inches
B. 6 inches
C. 12 inches
D. 24 inches
✅ Answer: C. 12 inches
Explanation: NEC 334.23 — NM cable within 6 ft of an attic scuttle must be
protected.

, 10. The minimum ampacity of a feeder for a 100A subpanel with continuous load of
80A is:


A. 80A
B. 100A
C. 125A
D. 150A
✅ Answer: C. 125A
Explanation: NEC 210.19(A)(1) — Continuous loads must be rated at 125% of the
load.


11. In Michigan, a Journeyman Electrician license requires at least how many hours
of practical experience?


A. 4,000
B. 6,000
C. 8,000
D. 10,000
✅ Answer: C. 8,000
Explanation: Michigan Electrical Code — 8,000 hours (4 years) of experience
required.


12. A disconnect for an air conditioner must be located:


A. Anywhere on the property
B. Within sight and readily accessible from the unit
C. Inside the dwelling
D. 50 ft away
✅ Answer: B. Within sight and readily accessible from the unit
Explanation: NEC 440.14 — The disconnecting means must be within sight and
readily accessible.

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
Alvon Chamberlain College Of Nursing
View profile
Follow You need to be logged in order to follow users or courses
Sold
61
Member since
4 year
Number of followers
20
Documents
856
Last sold
1 week ago
NURSING IS THE BEST

In This store You Find All Your Exammates In Handy............

4.2

5 reviews

5
2
4
2
3
1
2
0
1
0

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions