Question: what is the minimum size of threaded rod required for
sprinkler piping?
⼀Answer:⼀ 3/8 inch
Question: how often are fire department connections hydro-
statically tested?
⼀Answer:⼀ every 5 years
Question: sprinkler heads exposed to corrosive conditions are
covered with what?
⼀Answer:⼀ wax or lead
Question: automatic sprinkler systems have what color caps on the
fire department connections?
⼀Answer:⼀ green
Question: non automatic sprinkler systems have what color caps on
the fire department connections?
⼀Answer:⼀ silver
, Page | 2
Question: in a pressurized tank the water toair ratio is what
⼀Answer:⼀ 2 to 1 which means 2 parts water to 1 part air which
also means 66.33% water and 33.67%air
Question: sprinkler heads are factory tested at what psi?
⼀Answer:⼀ 400
Question: inspection records are maintained on site for how long?
⼀Answer:⼀ 3 years
Question: underwriters labs and factory mutual are what?
⼀Answer:⼀ testing companies
Question: a quick response sprinkler has an RTI ( response time
index) of what?
⼀Answer:⼀ 50
Question: a standard sprinkler has RTI of what?
⼀Answer:⼀ 80
Question: a sprinkler system with open heads is called a?
⼀Answer:⼀ Deluge system