Exam Questions and CORRECT Answers
4 wires - CORRECT ANSWER - what is the maximum number of 14 AWG RHH
conductors which can be installed in 1/2 rigid metal conduit?
3.5'-48" to the actuator - CORRECT ANSWER - Which of the following would be an
appropriate mounting height for a pull station?
1 flash per second - CORRECT ANSWER - What is the minimum flash rate for a visible
notification device?
90" to the top of the device - CORRECT ANSWER - What is the minimum mounting
height for audible notification devices?
Such that the entire lens is not less then 80" - CORRECT ANSWER - What is the
minimum mounting height for visible notification devices?
Voltage=Current X Resistence - CORRECT ANSWER - What is the formula for Ohm's
Law
Put your meter in series with the circuit - CORRECT ANSWER - When using your mult-
meter to measure, you must:
Semi-annually - CORRECT ANSWER - Waterflow devices shall be tested with that
frequency?
Annually - CORRECT ANSWER - With what frequency shall ionization smoke detectors
be given a functional test?
, 24 hours in normal operation, 5 minutes in alarm - CORRECT ANSWER - What are the
standby power requirements for a proprietary signaling system?
Shunt type - CORRECT ANSWER - Which of the following is a type of auxiliary
protective signaling system?
A UL listed central station
A receiver located at an unlisted monitoring facility
A fire department or communications center - CORRECT ANSWER - Remote station
signaling systems are permitted to send signals to:
600V - CORRECT ANSWER - Non-power limited fire alarm cable shall have an
insulation rating of:
20,000 CFM HVAC system serving a single floor
15,000 CFM HVAC system serving 3 floors
20,000 CFM HVAC system serving 2 floors - CORRECT ANSWER - Which of these
HVAC systems would require duct detectors on supply and return?
Group A, E, F - CORRECT ANSWER - According to the IBC, which of the following use
Groups require visual notification?
Every 4 hours - CORRECT ANSWER - Digital Alarm communicator transmitters
(DACT) which use call forwarding to the DACR shall be tested with what frequency?
True - CORRECT ANSWER - When connecting 4 wires smoke detectors to a fire alarm
system, the power conductors shall be monitored for integrity.
Smoke detectors shall be permitted to use 30 foot spacing as a guide - CORRECT
ANSWER - Which of the following is true regarding smoke detector spacing?