LATEST TEXAS EXT TYPE B TFM02
2025 BRAND NEW ACTUAL EXAM
WITH ANSWERS.
1. Low pressure cylinder - correct answer -when not specified,
shall be tested to factory test pressure, not exceeding 3x's
service pressure
2. Cartridge operated extinguishers - correct answer -tested at
original factory test pressure
3. High Pressure Cylinders - correct answer -DOT3A 3AA 3AL
cylinders tested @ 5/3 service pressure
4. CO2 extinguishers w/ ICC3 specs - correct answer -tested at
3000 psi
5. CO2 hose assemblies - correct answer -tested at 1250psi
, Page | 2
6. Dry Chem, Powder, water, foam, halogen hose assemblies -
correct answer -300psi or service pressure (whichever is
higher)
7. Low pressure accessory hose on wheeled extinguishers -
correct answer -tested at 300psi
8. High pressure hose on wheeled extinguishers - correct answer
-tested at 3000psi
9. Hose assemblies that pass hydrostatic testing - correct answer
-shall not requirerecording labeling or marking
10. Property owner - correct answer -assumes role of authority
having jurisdiction
11. Class a hazards - correct answer -travel distance is from any
point to extinguisher
, Page | 3
12. Class B, D, K hazards - correct answer -travel distance is
from hazard to extinguisher
13. HMIS - correct answer -Hazardous Material Identification
System
14. 13 seconds - correct answer -minimum discharge duration
for extinguisher rated at 2A or higher
15. Class A Hazard extinguishers - correct answer -water type,
halogenated, multipurpose dry chemical, wet chemical
16. Class B hazard extinguishers - correct answer -AFFF, FFFP,
CO2, Dry Chemical, Halogenated
17. Class a hazard installation minimum # of extinguishers -
correct answer -divide total floor area by maximum area to be
protected per extinguisher