If the MSSC for a BA is 800 MW, what is the DCS reporting threshold?
A) 240 MW
B) 640 MW
C) 840 MW
D) 300 MW - ✔✔B) 640 MW (80 %)
A BA that is part of a multiple BA Interconnection that is not receiving overlap regulation and uses a
fixed Frequency Bias Setting must have its calculated setting validated by the - ✔✔ERO (Electric
Reliability Organization)
The Frequency Bias Setting for a Balancing Area must be expressed in?
A) MW/0.1 Hz
B) MW/0.5 Hz
C) MW/0.01 Hz
D) MW/0.05 Hz - ✔✔A) MW/0.1 Hz
Units with nameplate ratings of _____ or greater should be equipped with governors.
,A) 25 MW
B) 15 MW
C) 10 MW
D) 50 MW - ✔✔C) 10 MW
There are how many ways to make adjustments for a time error correction?
A) 2
B) 3
C) 5
D) 6 - ✔✔A) 2
Who can serve as an Interconnection Time Monitor? - ✔✔Only Reliability Coordinators
BAs use ______ to automatically direct the loading of regulating reserves on their system. - ✔✔AGC
(Automatic Generation Control)
The MSSC for your BA is 650 MW. Your reporting threshold is > 520 MW. (650 x 80%). What is the
percent of recovery for the following situation?
Loss of a 575 MW unit
Pre-disturbance Ace = 150 MW
Post-recovery Ace = 10 MW - ✔✔+150 + (-575) = -425
, -425 + (x) = 10, x= 435
435/425= 100%
The MSSC for your BA is 650 MW. Your reporting threshold is >/equal to 520 MW. (650 x 80%) What is
the percent of recovery for the following situation?
Loss of a 600 MW unit
Pre-disturbance Ace = 150 MW
Post-recovery Ace = -50MW - ✔✔+150 + (-600) = -450
-450 + (x) = -50, x= 400
400/450= 89%
Units with nameplate ratings of 10 MW or greater should be equipped with governors which have a
droop of ______% - ✔✔5%,
All of the reasons listed below can be a cause of inadvertent accumulation except - ✔✔Market response
Each Balancing Area shall operate its AGC on ______, unless such operation is adverse to system or
Interconnection reliability. - ✔✔Tie-Line Frequency Bias
If a BA is unable to calculate ACE for more than _________ it shall notify its RC - ✔✔30 minutes
As a minimum, the BA must provide its System Operators with real-time values for all of the following
except ______ with each adjacent BA. - ✔✔MVAR flows