Courses DD101, DD102, and the BICSI RCDD Study Guide
"Which of the following consists of pre-manufactured
elastomeric components shaped to fit around standard cables,
tubes, conduits, and waveguides?"
A) Cable transit system
B) Fire-rated pathway device
C) Collar
D) Sleeve system Correct Answers A) Cable transit system
TDMM, 14th edition, Page 7-19
A backbone distribution shall have no more than ______ levels
of cross connections.
A) 1
B) 2
C) 3
D) 4 Correct Answers B) 2
TDMM, 14th edition, page 4-27
A continuous cable run should be _________________.
A) ≈5 m (16.5 ft)
B) ≈10 m (33 ft)
C) ≈30.5 m (100 ft)
D) ≈90 m (295 ft) Correct Answers C) ≈30.5 m (100 ft)
,TDMM, 14th edition, Page 5-71
A fire-rated pathway is categorized as which type of system?
A) Non-mechanical systems
B) Mechanical systems
C) Final Form
D) Pliable Form Correct Answers B) Mechanical systems
TDMM, 14th edition, page 7-19
A maximum of ____ connection points are allowed in the
channel
model.
A) two
B) three
C) four
D) five Correct Answers C) four
TDMM, 14th edition, Page 5-8
A maximum of ____ connection points are allowed in the
channel model.
A) two
B) three
C) four
D) five Correct Answers C) four
TDMM, 14th edition, Page 5-8
,A single MUTOA should be limited to serving a maximum of
__ work areas.
A) 5
B) 6
C) 10
D) 12 Correct Answers D) 12
TDMM, 14th edition, Page 5-27
A support shall also be placed within __________ on each side
of any connection to a fitting.
A) ≈152 mm (6 in)
B) ≈457 mm (18 in)
C) ≈0.6 m (2 ft)
D) ≈3 m (10 ft) Correct Answers A) ≈152 mm (6 in)
TDMM, 14th edition, Page 5-108
All equipment grounding conductors should be labeled to
indicate the:
(Select all that apply)
A) Grounding component
B) Ground bar
C) Telecommunications space
D) Building
E) A & B & C
F) B & C & D
, G) A & B Correct Answers E) A & B & C
A) Grounding component
B) Ground bar
C) Telecommunications space
TDMM, 14th edition, Page 10-34
Allow for a minimum of ____________ of clear vertical space
above
the cable tray for an overhead ceiling
cable tray.
A) ≈77 mm (3 in)
B) ≈152 mm (6 in)
C) ≈305 mm (12 in)
D) ≈457 mm (18 in) Correct Answers C) ≈305 mm (12 in)
TDMM, 14th edition, Page 5-94
Balanced twisted-pair cables have a nominal characteristic
impedance of ________ ohms at
100 MHz.
A) 25
B) 75
C) 100
D) 150 Correct Answers C) 100
TDMM, 14th edition, page 1-57