2025 UPDATED EXAM AND ANSWERS
4 wires - ANSWERS what is the maximum number of 14 AWG RHH conductors which can be
installed in 1/2 rigid metal conduit?
3.5'-48" to the actuator - ANSWERS Which of the following would be an appropriate mounting
height for a pull station?
1 flash per second - ANSWERS What is the minimum flash rate for a visible notification device?
90" to the top of the device - ANSWERS What is the minimum mounting height for audible
notification devices?
Such that the entire lens is not less then 80" - ANSWERS What is the minimum mounting height
for visible notification devices?
Voltage=Current X Resistence - ANSWERS What is the formula for Ohm's Law
Put your meter in series with the circuit - ANSWERS When using your mult-meter to measure,
you must:
Semi-annually - ANSWERS Waterflow devices shall be tested with that frequency?
, Annually - ANSWERS With what frequency shall ionization smoke detectors be given a
functional test?
24 hours in normal operation, 5 minutes in alarm - ANSWERS What are the standby power
requirements for a proprietary signaling system?
Shunt type - ANSWERS Which of the following is a type of auxiliary protective signaling system?
A UL listed central station
A receiver located at an unlisted monitoring facility
A fire department or communications center - ANSWERS Remote station signaling systems are
permitted to send signals to:
600V - ANSWERS Non-power limited fire alarm cable shall have an insulation rating of:
20,000 CFM HVAC system serving a single floor
15,000 CFM HVAC system serving 3 floors
20,000 CFM HVAC system serving 2 floors - ANSWERS Which of these HVAC systems would
require duct detectors on supply and return?
Group A, E, F - ANSWERS According to the IBC, which of the following use Groups require visual
notification?
Every 4 hours - ANSWERS Digital Alarm communicator transmitters (DACT) which use call
forwarding to the DACR shall be tested with what frequency?
True - ANSWERS When connecting 4 wires smoke detectors to a fire alarm system, the power
conductors shall be monitored for integrity.