1. How often shall the stem of an OS&Y Valve be lubricated: Annually
k k k k k k k k k k k
2. The 3 year dry pipe trip test is to be performed by whom?: MP & MFSPC
k k k k k k k k k k k k k k k
3. Fire department connections are to be inspected how often?: Quarterly
k k k k k k k k k
4. Water motor gongs are to be tested how often?: Quarterly
k k k k k k k k k
5. In a water spray fixed system inspection if the strainer is found corroded what color t
k k k k k k k k k k k k k k k
ag is required?: Yellow
k k k
6. A sprinkler head with a red frame has a temperature classification of?: Extra High (325 -
k k k k k k k k k k k k k k k
375°F)
k
7. The Hydraulic name plate shall be inspected how often?: Quarterly
k k k k k k k k k
8. What color tag is required when sprinkler heads are found to be lightly corroded?:
k k k k k k k k k k k k k k
Orange
9. Obstructions in sprinkler systems shall be investigated how often?: 5 Years k k k k k k k k k k
10. What color tag is required when the circuit breakers on a special service pump are o
k k k k k k k k k k k k k k k
ver 2 years old?: Orange
k k k k
11. What color tag is required when sprinkler heads made prior to 1920 have not been re
k k k k k k k k k k k k k k k
placed?: Orange, notify FDNY after 30 days
k k k k k k
12. During an operational test of a foam water sprinkler system, if the nozzles are plugged
k k k k k k k k k k k k k k
what color tag is used?: Red
k k k k k k
13. Steel water storage tanks without corrosive protection are to be inspected how often?:
k k k k k k k k k k k k
3 years
k k
14. A sprinkler head with a white frame has a temperature rating of?: 175 - 225°F
k k k k k k k k k k k k k k
15. The weekly test of an electric fire pump is how long?: 10 minutes
k k k k k k k k k k k k
16. The weekly test of a Diesel fire pump is how long?: 30 minutes
k k k k k k k k k k k k
17. Upon inspection of a sprinkler system, if the hydraulic nameplate is miss-
k k k k k k k k k k k
ing what color tag is used?: Yellow
k k k k k k k
18. When inspecting a preaction system, if the electrical components are not in service
k k k k k k k k k k k k k
what color tag is used?: Red
k k k k k
19. Vane type water flow devices shall be tested how often?: Semi-annually
k k k k k k k k k k
1k/k
13
, 20. Proper number of spare heads and wrenches shall be inspected how often?: Ann
k k k k k k k k k k k k
ually
21. The temperature rating of a sprinkler head with a green glass bulb is?: 175
k k k k k k k k k k k k k
- 225°F k
22. When inspecting a sprinkler system if the spare sprinkler cabinet is miss-
k k k k k k k k k k k
king what color tag should be used?: Yellow
k k k k k k k
23. On a dry pipe sprinkler head if no tests were conducted in 12 years what color tag sh
k k k k k k k k k k k k k k k k k
ould be used?: Orange
k k k
24. Red Tag: Impairment (Notify FDNY, shall be fixed immediately)
k k k k k k k k
25. Orange Tag: Critical Deficiency (Notify FDNY if not fixed after 30 days)
k k k k k k k k k k k
2k/k
13