1. All work performed on any component of a fire sprinkler system MUST be done by or u
d d d d d d d d d d d d d d d d
nder the supervision of a: G. Card holder
d d d d d d d
2. Quarterly Inspections MUST be done by a: License holder or designee
d d d d d d d d d d
3. Service Tags SHALL be hung on the: OS&Y valve after work is completed
d d d d d d d d d d d d
4. The minimum number of heads in a box is: Six
d d d d d d d d d
5. The maximum working pressure of a fire sprinkler system is: 175psi
d d d d d d d d d d
6. A dry pipe valve and supply pipe SHALL be protected from: Freezing
d d d d d d d d d d d
7. How much notice must be given to the AHJ before a test or inspection can be scheduled
d d d d d d d d d d d d d d d d
?: 48 hoursd d
8. When a fire sprinkler system has more than 20 sprinkler heads a: Fire alarm is required
d d d d d d d d d d d d d d d
9. A fire sprinkler system MUST take no longer than
d d d d d d d d d
for water to reach the most remote head: 3 minutes
d d d d d d d d d
10. What is the minimum residual pressure required for a light hazard fire sprinkler sy
d d d d d d d d d d d d d
stem?: 15psi d
11. The air pressure over the anticipated trip pressure of a dry fire sprinkler system shou
d d d d d d d d d d d d d d
ld not exceed: 20psi
d d d
12. The maximum length of lateral sway bracing on a cross main is: 40 feet
d d d d d d d d d d d d d
13. Pipe hangers SHALL be designed to hold the weight of the pipe filled with water plus: 2
d d d d d d d d d d d d d d d d
50lbs at the point of the hanger
d d d d d d
14. The all thread required to hang 5, 6 & 8 inch pipe is: 1/2"
d d d d d d d d d d d d d
15. Fire sprinkler system piping SHALL be tested at 200psi for: 2 hours
d d d d d d d d d d d
16. The water gauge SHALL be placed above and below the: Alarm check valve
d d d d d d d d d d d d
17. E.S.F.R (early suppression fast response) sprinkler heads are NOT allowed in: Dry syste
d d d d d d d d d d d d
ms
18. Maintenance and inspection of fire sprinkler systems is found in: NFPA 25 d d d d d d d d d d d
19. T or F : NFPA 13 is for design, installation and water supply only: False
d d d d d d d d d d d d d d
20. Upright head frames MUST be installed d to branch lines: Verticald d d d d d d d
21. Maximum temperature of water inside a fire sprinkler pipe: 120 Degrees d d d d d d d d d d
1d/d3