ANSWERS 100% CORRECT!
, Insecticidal fogging operations are hazardous because the chemicals... - ANSWER May
be toxic
A fire watch must be provided when a(n)____ is out of service - ANSWER standpipe
systems
An impairment coordinating is the person responsible to notify the fire department about
an out-of-service fire protection system condition. Who should legally designate the
impairment coordinator?.. - ANSWER the building owner
Select the correct statement regarding battery systems. (refer to the reference table) -
ANSWER The B-29 Certificate of fitness holder is responsible to perform periodically
visual inspection of the battery system
Who is responsible to maintain the pre-hot work check record? - ANSWER the
responsible person for the hot work
Phase 1 elevator emergency recall operation must be activated______. - ANSWER
automatically when smoke detectors or the sprinkler waterflow alarms are activated
Select the correct statement regarding the record keeping of refrigeration system
operation. - ANSWER The logbook must include entries of any operating problems or
deficiencies, and required periodic tests conducted
Which of the following building occupancies requires an EPA director to implement the
emergency action plan? - ANSWER An office building greater then 75 feet high
The only Q-01 certificate of qualification holder on duty in the building is asked by the
Chief Engineer to leave the building to purchase a plumping tool. what immediate action
should the Q-01 certificate of qualification holder take consistent with the new york city
fire code? - ANSWER Not leave the building when the refrigerating system is in
operation
The sprinkler system in a machinery room containing a refrigerating system is out of
service. under this condition, hot work operations_____. - ANSWER Are prohibited in
that area
Transfer switches of the emergency power system must be tested semiannually. which
is the correct statement regarding the testing procedure? - ANSWER electrically
operate the switch from the standard position to the alternate position and then return
back to the standard position.