NEC practical Practice Test (PART 2) 2024
2024/25 NEC Review Practice Test
A disconnecting means for a 2,300-volt motor must be capable of being locked in the open
position.
1.
a) True
b) False
The branch circuit overcurrent device may serve as the disconnecting means for stationary
motors rated less than one horsepower.
2.
a) True
b) False
## CORRECT --> For stationary motors of 1/8 hp or less, the branch-circuit overcurrent device shall be permitted to
serve as the disconnecting means.
A motor controller shall open all conductors to the motor.
3.
a) True
b) False
## CORRECT --> The controller shall not be required to open all conductors to the motor.
In general, enclosures for motor controllers shall not be used as junction boxes unless designs
are employed that provide adequate space for this purpose.
4.
True
a)
b) False
## CORRECT --> Enclosures for motor controllers and disconnecting means shall not be used as junction boxes,
auxiliary gutters, or raceways for conductors feeding through or tapping off to the other apparatus unless designs are
employed that provide adequate space.
Heating panels for de-icing must not exceed a rating of 120-watts/square foot.
5.
, lOMoAR cPSD| 47061011
b) False
## CORRECT --> There are also heating panel requirements for space heating in Article 424.
Excess leads of heating cables must not be cut.
6.
a) True
b) False
## CORRECT --> Excess leads of heating cables shall not be cut but shall be secured to the underside of the ceiling
and embedded in plaster or other approved material, leaving only a length sufficient to reach the junction box with
not less than 6 in. (152 mm) of free
In most cases, heating cables installed on ceiling boards must be secured at intervals not
exceeding 16 inches.
7.
a) True
b) False
## CORRECT --> Cables shall be secured by means of approved stapling, tape, plaster, nonmetallic spreaders, or
other approved means at either intervals not exceeding 16 in. (406 mm) or at intervals not exceeding 6 ft (1.83 m) for
cables identified for such use.
Conductors located above a heated ceiling are considered to operate in a 40 degrees C ambient.
8.
a) True
b) False
## CORRECT --> Wiring located above heated ceilings shall be spaced not less than 2 in. (50.8 mm) above the heated
ceiling and shall be considered as
The non heating leads of 120-volt space heating cables are yellow,
9.
a) True
b) False
Unit switches may disconnect a heater if other means of disconnection are provided.
10.
a) True
b) False
## CORRECT --> A unit switch(es) with a marked “off” position that is part of a fixed heater and disconnects all
ungrounded conductors shall be permitted as the disconnecting means required by this article where other means for
, lOMoAR cPSD| 47061011
A cord and plug may be the disconnecting means for a wall-mounted electric oven.
11.
a) True
b) False
Dishwashers shall be connected with Type SP-1 flexible cords.
12.
a) True
b) False
## CORRECT --> Built-in dishwashers and trash compactors shall be permitted to be cord- and plug-connected with
a flexible cord identified as suitable for the purpose in the installation instructions of the appliance manufacturer.
Flexible cords are permitted only to supply portable appliances.
13.
a) True
b) False
Toasters may have live parts exposed to contact.
14.
a) True
b) False
## CORRECT --> Appliances shall have no live parts normally exposed to contact other than those parts functioning
as open-resistance heating elements, such as the heating element of a toaster, which are necessarily exposed.
The conductor between the surge arrester and the line and the surge arrester and the grounding
connection shall not be smaller than 6 AWG copper or aluminum.
15.
a) True
b) False
## CORRECT --> Line and ground connecting conductors shall not be smaller than 6 AWG copper or aluminum.
If a generator operates at 30-volts, protection of live parts is required when the generator is
accessible to unqualified persons.
16.
a) True
b) False
, lOMoAR cPSD| 47061011
The nominal voltage of a lead-acid battery is 2.0 volts per cell.
17.
a) True
b) False
A capacitor operating at 300-volts must be discharged to 50-volts or less within one minute
after it is disconnected from the supply.
18.
a) True
b) False
Capacitor circuit conductors must have an ampacity at least 125% of the rated current of the
capacitor.
19.
a) True
b) False
## CORRECT --> 135% is the requirement.
Potential or voltage transformers installed indoors require primary fuses.
20.
a) True
b) False
2008 NEC Review Practice Test 9
The branch circuit load for a 12-kilowatt electric range in a dwelling is 8-kilowatts.
1.
a) True
b) False
An appliance always requires a disconnecting means.
2.
a)
True