Under which TWO circumstances are the operating times of RCD's required to be tested? - correct
answer Where the RCD is used for:
1. Fault Protection against indirect contact (the 1 x test)
OR
2. Additional Protection against direct contact (the 5 x test)
For each test, why does the RCD need to be tested on the positive and negative half cycles? - correct
answer Because each half cycle may produce a different test result
If testing on each half cycle produces a different test result, which test result is recorded? - correct
answer The longer operating time
Prior to RCD testing which other test MUST have been carried out? - correct answer
Earth Fault Loop Impedance
Why must EFLI testing have been carried out before RCD testing? - correct answer
To prove there is a satisfactory earth path for the test current to flow down
If an RCD test was performed on a circuit without a satisfactory earth path, what danger would occur? -
correct answer The risk of electric shock to anyone in contact with
exposed/extraneous conductive parts during the test.
Which test instrument is used for RCD testing? - correct answer An RCD tester
Where is the RCD test carried out? - correct answer On the load side of the RCD
Between which conductors is the RCD test carried out? - correct answer Line and
cpc