Heat exchanger shall be checked for - -Cooling water flow
- All alarm pilot lights should be in what state - -Off
- There are two requirements listed under pump house conditions. What are
they? - -Ventilating louvers are free to operate and heat pump is adequate
not less than 40°F for diesel pump rooms
- Weekly inspection requires verification that the pump suction discharge
and bypass valves should be fully open - -True
- When verifying the electrical system conditions, the controller pilot light
should be - -Green
- Diesel engine, fuel tank level float switch and solenoid valve operation
shall be checked - -Weekly visual inspection
- What kind of pump do you record the time to crank? - -Diesel
- The pertinent visual observation categories is required to be inspected.
Weekly checklist are. - -Pump, house, conditions, pump, system, conditions,
electrical systems conditions, diesel, engine system, conditions, and steam
engine conditions
- What is the purpose of inspecting the pump assembly? - -Appears to be an
operating condition and is free from physical damage
- The transfer switch normal pilot light should be - -Illuminated
- The isolating switch for electrical pumps should be - -Closed
- Pump packing boxes, bearings, and casings shall be checked for - -
Overheating
- The reverse phase alarm pilot light for electric pumps should be - -Off
- The purpose of testing the pump assembly is to ensure automatic manual
operation upon demand and continuous delivery of the required system
output and additional purpose is to detect - -Deficiencies not evident by
inspection
and A’s
Heat exchanger shall be checked for - -Cooling water flow
- All alarm pilot lights should be in what state - -Off
- There are two requirements listed under pump house conditions. What are
they? - -Ventilating louvers are free to operate and heat pump is adequate
not less than 40°F for diesel pump rooms
- Weekly inspection requires verification that the pump suction discharge
and bypass valves should be fully open - -True
- When verifying the electrical system conditions, the controller pilot light
should be - -Green
- Diesel engine, fuel tank level float switch and solenoid valve operation
shall be checked - -Weekly visual inspection
- What kind of pump do you record the time to crank? - -Diesel
- The pertinent visual observation categories is required to be inspected.
Weekly checklist are. - -Pump, house, conditions, pump, system, conditions,
electrical systems conditions, diesel, engine system, conditions, and steam
engine conditions
- What is the purpose of inspecting the pump assembly? - -Appears to be an
operating condition and is free from physical damage
- The transfer switch normal pilot light should be - -Illuminated
- The isolating switch for electrical pumps should be - -Closed
- Pump packing boxes, bearings, and casings shall be checked for - -
Overheating
- The reverse phase alarm pilot light for electric pumps should be - -Off
- The purpose of testing the pump assembly is to ensure automatic manual
operation upon demand and continuous delivery of the required system
output and additional purpose is to detect - -Deficiencies not evident by
inspection