Installation & Maintenance with Correct
Solutions
The point of transfer at a dispensing unit must be ____ from Public ways, including
public streets, highways, thoroughfares, and sidewalks.
A. 10 feet
B. 15 feet
C. 25 feet - ANSWER-A. 10 feet
Steel supports on vertical ASME containers shall be protected against fire exposure
with a material having a fire resistance rating of a least _____, except that continuous
steel skirts that have only one opening that is 18 in. or less in diameter shall have fire
protection applied to the ______ of the skirts.
A. 3 hrs; outside
B. 2 hrs; outside
C. 3 hrs; inside - ANSWER-B. 2 hrs; outside
Pressure relief devices installed in underground containers serving dispensing systems
shall be piped vertically upward to a point at least _____ above the ground.
A. 2 feet
B. 6 feet
C. 10 feet - ANSWER-C. 10 feet
A remote emergency shut off device for either the internal valve or emergency shutoff
valve is required to be located not less than _____ or more than _____ from the liquid
transfer point.
A. 10 ft ; 50ft
B. 10 ft; 100ft
C. 3 ft; 100ft - ANSWER-C. 3 ft; 100ft
A person or business may not dispense propane to the consumer without a _______.
A. Proper Training
B. A picture of your Instructor
C. A License - ANSWER-C. A License