spacing for smoke detectors or manufactured specs Answer - rule of thumb -
30ft
manual pull station height Answer - 3-1/2 to 4-1/2 ft
secondary power must turn of within ? seconds on loss of primary supply
Answer - 10 seconds
manual pull stations must be mounted within ? feet of exits on each floor and
spaced up to ? Answer - 5 ft, 200 ft
residential, secondary power supply time Answer - 24 hours in normal, 4
minutes of full alarm
commercial, secondary power supply time Answer - 24 hours in normal, 5
minutes of full alarm
live voice, secondary power supply time Answer - 24 hours in normal, 15
minutes of full power
audible device decibels, public Answer - 75 db minimum or 15 above ambient
audible device decibels, private Answer - 45 db or 15 db above ambient