Questions and CORRECT Answers
Internatioal system of units - CORRECT ANSWER✔✔- Metric
Extinguisher Service Pressure - CORRECT ANSWER✔✔- Normal Operating pressure
Factory test pressure - CORRECT ANSWER✔✔- Pressure at which the shell was tested at
time of manufacture
Recharging - CORRECT ANSWER✔✔- Replacement of exstinguishing agent
Servicing - CORRECT ANSWER✔✔- Performing maintenance
Travel Distence - CORRECT ANSWER✔✔- Actual distence traveled to nearest FE
Cartridge/ cylinder operated - CORRECT ANSWER✔✔- FE where gas is stored seperate
from agent
Nonrechargable FE - CORRECT ANSWER✔✔- FE not capable of undergoing maintenance
Class A - CORRECT ANSWER✔✔- Ordinary combustible materials
Class B - CORRECT ANSWER✔✔- Flammable liquids
Class C - CORRECT ANSWER✔✔- Fires that include Energized Electrical equipment
Class D - CORRECT ANSWER✔✔- Combustible Metals
Class K - CORRECT ANSWER✔✔- Kitchen Fire
, Classifying Occupancy Hazard - CORRECT ANSWER✔✔- Rooms/ areas are to be
classified as light, ordinary, or extra
Class B Selection - CORRECT ANSWER✔✔- Shall be made by recomandation of
specialized equipment Manufacturer
3D fire - CORRECT ANSWER✔✔- 10 lb or greater with discharge rate of 1lb/sec or more
shall be used
Cooking Media - CORRECT ANSWER✔✔- Class K shall be used on appliances using
cooking media (vegetable or animal oils/ fats)
Installation height less than 40lb - CORRECT ANSWER✔✔- Top of FE cannot exceed 5ft
Installation height more than 40lb - CORRECT ANSWER✔✔- Top of Fe cannot exceed 3
1/2 ft
Installation height from floor - CORRECT ANSWER✔✔- In no case can it be less than 4
inches
Calcium Chloride - CORRECT ANSWER✔✔- can not be used in stainless steel FE
Travel Distance for K - CORRECT ANSWER✔✔- 30 ft
FE visual Inspection - CORRECT ANSWER✔✔- every 30 day i
Carbon Dioxide Hose Assemblies - CORRECT ANSWER✔✔- Requires Conductivity Test
Pressure Regulators - CORRECT ANSWER✔✔- Provided with Wheeled FE's shall be tested
annually for outlet static pressure and flow rate