4 wires - Answer✔✔-what is the maximum number of 14 AWG RHH conductors which can be installed in
1/2 rigid metal conduit?
3.5'-48" to the actuator - Answer✔✔-Which of the following would be an appropriate mounting height
for a pull station?
1 flash per second - Answer✔✔-What is the minimum flash rate for a visible notification device?
90" to the top of the device - Answer✔✔-What is the minimum mounting height for audible notification
devices?
Such that the entire lens is not less then 80" - Answer✔✔-What is the minimum mounting height for
visible notification devices?
Voltage=Current X Resistence - Answer✔✔-What is the formula for Ohm's Law
Put your meter in series with the circuit - Answer✔✔-When using your mult-meter to measure, you
must:
Semi-annually - Answer✔✔-Waterflow devices shall be tested with that frequency?
Annually - Answer✔✔-With what frequency shall ionization smoke detectors be given a functional test?
Page 1/9
, EMILLYCHARLOTTE 2024/2025 ACADEMIC YAER ©2024 EMILLYCHARLOTTE. ALL RIGHTS RESERVED
FIRST PUBLISH SEPTEMBER 2024
24 hours in normal operation, 5 minutes in alarm - Answer✔✔-What are the standby power
requirements for a proprietary signaling system?
Shunt type - Answer✔✔-Which of the following is a type of auxiliary protective signaling system?
A UL listed central station
A receiver located at an unlisted monitoring facility
A fire department or communications center - Answer✔✔-Remote station signaling systems are
permitted to send signals to:
600V - Answer✔✔-Non-power limited fire alarm cable shall have an insulation rating of:
20,000 CFM HVAC system serving a single floor
15,000 CFM HVAC system serving 3 floors
20,000 CFM HVAC system serving 2 floors - Answer✔✔-Which of these HVAC systems would require duct
detectors on supply and return?
Group A, E, F - Answer✔✔-According to the IBC, which of the following use Groups require visual
notification?
Every 4 hours - Answer✔✔-Digital Alarm communicator transmitters (DACT) which use call forwarding to
the DACR shall be tested with what frequency?
True - Answer✔✔-When connecting 4 wires smoke detectors to a fire alarm system, the power
conductors shall be monitored for integrity.