if a combination audible/visible appliances are installed, the location of the installed appliance shall be
determined by the requirements of - Answer✔✔-the visible appliance
what is the maximum number of 12-gaugeTHHN conductors that can be installed in 1-inch EMT -
Answer✔✔-26
Do you resistors are connected in parallel. R1 = 300 Ohms, R2 = 300 Ohms. What is the equivalent
resistance? - Answer✔✔-150 Ohms
I room is 200 feet long and 100 feet wide, and the 8 foot high ceiling is smooth and flat. A spot-type heat
detector has been selected that is listed for a 50 foot maximum spacing between detectors. According to
NFPA 72, how many detectors will be needed to protect this room? - Answer✔✔-12
Fire warning equipment to be installed and residential occupancy's child produced audible emergency
evacuation signal described in - Answer✔✔-ANSI S3.41
According to NFPA 72, the minimum number of restorable fixed-temperature spot-type heat detectors
that must be tested during each annual test is - Answer✔✔-Two detectors are more on each initiating
device circuit
According to, how many spot type heat detectors are required for a space that is 80 foot long and 55-
foot wide with a smooth 10 foot ceiling? The heat detector is listed for a maximum space between
detectors of 30 feet. - Answer✔✔-6