NICET Fire Alarm Level 1 Exam Practice Questions and Answers|100% Pass When a device is inaccessible due to excessive height, such as an atrium, what it the maximum interval for testing? - Answer-18 months When installing a wall-mounted fire telephone appliance to the public, what is the acceptable maximum mounting height from the floor? - Answer-66 inches Elevator lobby smoke detectors shall be mounted within a maximum of which distance from the center- line of the door? - Answer-21 feet At minimum, when working near power lines with voltage of 600 volts and lower, an aerial lift operator shall maintain which distance from the lines? - Answer-10 feet The use of unprotected EMT shall be permitted under which conditions? - Answer-when in direct contact with the earth According to NFPA 70, what is the maximum unsupported length of 1/2-inch flexible metallic conduit where flexibility is required after installation? - Answer-4 1/2 feet What is the maximum bend (in degrees) permitted in a conduit run between outlet boxes? - Answer- 360 Degrees EMILLYCHARLOTTE 2024/2025 ACADEMIC YAER ©2024 EMILLYCHARLOTTE. ALL RIGHTS RESERVED FIRST PUBLISH SEPTEMBER 2024 Page 2/11 If the primary power is disconnected and the fire alarm system goes into an alarm condition, what is the minimum acceptable time for secondary power to operate the voice evacuation systems? - Answer- 15 minutes A riser room temperature switch should activate when the temperature falls below which level? - Answer-40 degrees F According to NFPA 72, what is the maximum sound pressure level permitted in a space with notification appliances? - Answer-110 dBA What is the minimum interval for testing a single-station smoke detector in multifamily units? - Answer-Annually Where should a technician install a detector in relation to beam that is less than 12 inches deep and less that 8 feet in center? - Answer-At the bottom of the beam An existing fire alarm cable in a drop ceiling will be spliced. which one of the following splice locations will comply with NFPA 70? - Answer-secured inside a listed box or enclosure Which function shall be tested for each newly installe

Show more Read less
Institution
Nicet
Course
Nicet









Whoops! We can’t load your doc right now. Try again or contact support.

Written for

Institution
Nicet
Course
Nicet

Document information

Uploaded on
October 6, 2024
Number of pages
11
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

Content preview

EMILLYCHARLOTTE 2024/2025 ACADEMIC YAER ©2024 EMILLYCHARLOTTE. ALL RIGHTS RESERVED
FIRST PUBLISH SEPTEMBER 2024




NICET Fire Alarm Level 1 Exam Practice
Questions and Answers|100% Pass

When a device is inaccessible due to excessive height, such as an atrium, what it the maximum interval

for testing? - Answer✔✔-18 months


When installing a wall-mounted fire telephone appliance to the public, what is the acceptable maximum

mounting height from the floor? - Answer✔✔-66 inches


Elevator lobby smoke detectors shall be mounted within a maximum of which distance from the center-

line of the door? - Answer✔✔-21 feet


At minimum, when working near power lines with voltage of 600 volts and lower, an aerial lift operator

shall maintain which distance from the lines? - Answer✔✔-10 feet


The use of unprotected EMT shall be permitted under which conditions? - Answer✔✔-when in direct

contact with the earth


According to NFPA 70, what is the maximum unsupported length of 1/2-inch flexible metallic conduit

where flexibility is required after installation? - Answer✔✔-4 1/2 feet


What is the maximum bend (in degrees) permitted in a conduit run between outlet boxes? - Answer✔✔-

360 Degrees




Page 1/11

, EMILLYCHARLOTTE 2024/2025 ACADEMIC YAER ©2024 EMILLYCHARLOTTE. ALL RIGHTS RESERVED
FIRST PUBLISH SEPTEMBER 2024


If the primary power is disconnected and the fire alarm system goes into an alarm condition, what is the

minimum acceptable time for secondary power to operate the voice evacuation systems? - Answer✔✔-

15 minutes


A riser room temperature switch should activate when the temperature falls below which level? -

Answer✔✔-40 degrees F


According to NFPA 72, what is the maximum sound pressure level permitted in a space with notification

appliances? - Answer✔✔-110 dBA


What is the minimum interval for testing a single-station smoke detector in multifamily units? -

Answer✔✔-Annually


Where should a technician install a detector in relation to beam that is less than 12 inches deep and less

that 8 feet in center? - Answer✔✔-At the bottom of the beam


An existing fire alarm cable in a drop ceiling will be spliced. which one of the following splice locations

will comply with NFPA 70? - Answer✔✔-secured inside a listed box or enclosure


Which function shall be tested for each newly installed smoke detector? - Answer✔✔-smoke entry?


An 180 foot long corridor is 10 feet wide, with a smooth 10 foot ceiling, interrupted by 4-inch beams

spaced every 10 feet. How many heat detectors with a listed 30 foot spacing are required? - Answer✔✔-

6 heat detectors


At which height must cables be physically protected when being installed within an exposed ceiling? -

Answer✔✔-7 feet




Page 2/11

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
EmillyCharlotte Howard Community College
View profile
Follow You need to be logged in order to follow users or courses
Sold
94
Member since
1 year
Number of followers
4
Documents
11951
Last sold
2 days ago
ALL-MAJOR.

On this page, you find all documents, package deals, and flashcards offered by seller Emilly Charlotte.

3.6

20 reviews

5
7
4
6
3
2
2
2
1
3

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions