Holt, Electricians Exam Prep, Unit
6(Latest Exam 2024)
Conductor Insulation Properties: Table _____ of the NEC
provides information on conductor properties such as
permitted use, maximum operating temperature and
other insulation details. - correct answers✅310.104(a)


TW can be described as thermoplastic insulation, suitable
for dry or wet locations with a maximum operating
temperature of 60 degrees C(True/False) - correct
answers✅True


TFFN can be described as stranded fixture wire with
thermoplastic insulation, nylon cover. (True/False) -
correct answers✅True


The ampacity of a conductor is listed in table _____ under
the condition of no more than three current carrying
conductors bundled together in raceway, cable or earth
an ambient temperature of 86 degrees F. - correct
answers✅310.15(b)(16)


The ampacities listed in Table 310.15(b)(16) are based on
temperature alone and do not take _____ into account. -
correct answers✅Voltage drop


Voltage drop considerations are for ________ and not for
safety; therefore, sizing conductors for voltage drop is not

,Holt, Electricians Exam Prep, Unit
6(Latest Exam 2024)
a Code requirement. - correct answers✅Efficiency of
operation


The smallest size conductor permitted by the NEC for
branch circuits, feeders or services is _____ copper or
_____ aluminum. - correct answers✅No. 14, No. 12


When selecting a conductor for a circuit, always select
the conductors not smaller than the _______ of the
equipment. - correct answers✅Terminal ratings


(110-14(c)(1) ) Equipment rated at 100 ampere or less
shall have the conductor sized no smaller than _____
degrees C unless the terminals are marked otherwise. -
correct answers✅60


(110-14(c)(1) )What size THHN conductor is required for a
50 ampere circuit, listed for use at 60 degrees C? -
correct answers✅No. 6


What size THHN conductor is required for a 50 ampere
circuit, listed for use at 75 degrees C? - correct
answers✅No. 8

,Holt, Electricians Exam Prep, Unit
6(Latest Exam 2024)
(110-14(c)(2) )Terminals for equipment rated over 100
ampere and pressure connector terminals for conductors
larger than No. 1 shall have the conductor sized
according to the _____ temperature rating listed in Table
310.15(B)(16) - correct answers✅75 degree


What size THHN conductor is required to supply a 225
ampere feeder? - correct answers✅4/0


Parallel conductors (electrically joined at both ends)
permit a smaller ________ per ampere. This can result in a
significant cost savings for circuits over 300 amperes. -
correct answers✅Cross-sectional area


What size 75 degree C conductors are required for a 600
ampere service that has a calculated demand load of 550
amperre? - correct answers✅1250 kcmil


What size conductors(2) would be required in one
raceway (nipple) for a 600 ampere service? The
calculated demand load is 550 ampere. - correct
answers✅300 kcmil


When equipment grounding conductors are installed with
circuit conductors that are run in parallel, each raceway
must have an equipment grounding conductor sized

, Holt, Electricians Exam Prep, Unit
6(Latest Exam 2024)
according to the overcurrent protection device protecting
the circuit.(True/False) - correct answers✅True


What size equipment grounding conductor is required in
each of two raceways for a 600 ampere feeder?(Table
250.122) - correct answers✅No. 1


Overcurrent protection devices have two ratings,
overcurrent and _________. - correct answers✅Ampere
interrupting current(AIC)


Ampere interrupting current (AIC) is for short circuit
faults. They are meant to protect a device from _______
while trying to clear a fault. - correct
answers✅Exploding


The minimum interruption rating is _____ ampere for
circuit breakers and _____ ampere for fuses. - correct
answers✅5000, 10000


Continuous Load Protection: Overcurrent protections
devices are sized at no less than ____ percent of the
continuous load, plus _____ percent of the noncontinuous
load. - correct answers✅125, 100

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
chloemurimi Keiser University
Follow You need to be logged in order to follow users or courses
Sold
196
Member since
3 year
Number of followers
175
Documents
1457
Last sold
2 months ago
Expertsminds

Helping students not just improving grades but also to provide better learning of subject concepts and its problem statements. I am providing you world class assistance which may help you to excel in course or assignments.

4.0

37 reviews

5
20
4
5
3
7
2
3
1
2

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions