Update Questions with Correct Answers
A - Answer -A category 8 cable is terminated into category 6A outlets with category 5e patch cords.
What is the maximum supported performance level?
A Category 5e
B Category 6A
C Category 7
D Category 8
A - Answer -A grey backboard should be used to identify _____ backbone cable?
A Second-level
B Intrabuilding
C First-level
A - Answer -A purple backboard should be used to identify ________?
A Common equipment
B Demarcation point
C Network connections
D Horizontal cable
,A - Answer -A radio station transmits an omnidirectional signal that is received by multiple radios.
What type of transmission method is used in this example?
A Simplex
B Half-duplex
C Full-duplex
A - Answer -A third 90-degree bend may be permitted in a conduit run if one of the bends is
located within ____ of the cable feed end?
A 300 mm (12")
B 375 mm (15")
C 450 mm (18")
D 483mm (19")
A - Answer -Cavity boxes should be at least _____ away from the wall, where possible.
A 100mm (4")
B 150mm (6")
C 300mm (12")
D 450mm (18")
A - Answer -During the troubleshooting phase, what is the first step?
,A Verify
B Isolate
C Repair
D Test
A - Answer -How long does it take someone to form a first impression?
A 10 to 15 seconds
B 1 to 2 minutes
C 5 to 10 minutes
D 30 minutes to 1 hour
A - Answer -If the situation requires, a conduit should be terminated _______ the plywood
backboard?
A Through
B Above
C Below
A - Answer -If you are working on a catwalk, you are required to wear _____?
A Full body harness and two lanyards
B Nothing, your fine on the catwalk
, C Safety belt
A - Answer -Light pulses in optical fiber cables are subjected to a loss in power as the light pulses
travel along the optical fiber. Which of the
following terms is used to describe this phenomenon?
A Attenuation
B Grounding
C Crosstalk
D Frequency
A - Answer -What grade of plywood is recommended for use with ICT systems?
A A/C
B A/D
C C/D
D B/C
A - Answer -What is the bend radius requirement for optical fiber cable when the cable is at rest?
A 10 times the cables outside diameter
B 15 times the cables outside diameter
C 20 times the cables outside diameter