Where Public Mode audible appliances are installed they shall be ____________ above average ambient sound level Correct Answer 15dba Where audible appliances are installed in mechanical equipment rooms, the average ambient sound level is Correct Answer 85dba An average ambient sound level greater than ______ shall require the use of a visible notification appliance Correct Answer 105dba All fire detection devices shall be listed or approved for the purpose for which they are intended Correct Answer True A detector should not be recessed in any way unless they have been tested for such a mounting Correct Answer True How far from the doorway shall a Manual fire alarm station be mounted Correct Answer 5' Vane type flow switch have no longer than _____ to initiate alarm Correct Answer 90 sec smoke detectors must be tested every Correct Answer 1 year Sensitivity in smoke detectors and single & multiple-station smoke alarms in other than 1&2 family dwellings shall be checked within _____ year or years after installation Correct Answer 1 year A spot-type heat detector located on a wall shall not be more than _____ inches from the ceiling Correct Answer 12'' With a peak ceiling, heat and smoke detectors shall be located within _____ of the peak, measured horizontally Correct Answer 36'' smoke detectors shall not be located near Correct Answer Air supply diffusers When beams project more than _____ inches below the ceiling and are more than 8' on center, each bay formed by the beams shall be treated as a separate area for heat detectors Correct Answer 18'' When manual fire alarm boxes are used, the distance between boxes will not be in excess of Correct Answer 200'

Show more Read less
Institution
Ohio Fire Alarm
Course
Ohio fire Alarm









Whoops! We can’t load your doc right now. Try again or contact support.

Written for

Institution
Ohio fire Alarm
Course
Ohio fire Alarm

Document information

Uploaded on
August 30, 2024
Number of pages
10
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

Content preview

Ohio fire Alarm Questions with 100%
Correct Answers
Where Public Mode audible appliances are installed they shall be ____________ above
average ambient sound level Correct Answer 15dba

Where audible appliances are installed in mechanical equipment rooms, the average
ambient sound level is Correct Answer 85dba

An average ambient sound level greater than ______ shall require the use of a visible
notification appliance Correct Answer 105dba

All fire detection devices shall be listed or approved for the purpose for which they are
intended Correct Answer True

A detector should not be recessed in any way unless they have been tested for such a
mounting Correct Answer True

How far from the doorway shall a Manual fire alarm station be mounted Correct Answer
5'

Vane type flow switch have no longer than _____ to initiate alarm Correct Answer 90
sec

smoke detectors must be tested every Correct Answer 1 year

Sensitivity in smoke detectors and single & multiple-station smoke alarms in other than
1&2 family dwellings shall be checked within _____ year or years after installation
Correct Answer 1 year

A spot-type heat detector located on a wall shall not be more than _____ inches from
the ceiling Correct Answer 12''

With a peak ceiling, heat and smoke detectors shall be located within _____ of the
peak, measured horizontally Correct Answer 36''

smoke detectors shall not be located near Correct Answer Air supply diffusers

When beams project more than _____ inches below the ceiling and are more than 8' on
center, each bay formed by the beams shall be treated as a separate area for heat
detectors Correct Answer 18''

When manual fire alarm boxes are used, the distance between boxes will not be in
excess of Correct Answer 200'

, A water flow device should be field adjusted so that an alarm is initiated in no more than
_____ seconds Correct Answer 90 seconds

smoke detectors shall not be located directly in the air stream of Correct Answer supply
registers

Detectors shall not be installed until after Correct Answer Final clean up of all trades

a heat detector integrally mounted on a smoke detector shall be listed and approved for
not less than Correct Answer 50'

Detectors for common return systems should be installed up to ______ in front or
behind openings Correct Answer 12''

A line-type obsucration smoke detector, where the light beam is projected across the
area to be protected Correct Answer projected beam smoke detector

A device which detects the visible particles of combustion is a ____ detector Correct
Answer Smoke

Manual Fire alarm boxes shall not be less than _______ inches and not more than
______ inches above the floor level Correct Answer 42/48

single and multiple stations smoke alarms shall be tested after the initial installation test
every ____ Correct Answer 1 year

smoke detectors installed within _______ feet of cooktop or range must be of the _____
type Correct Answer 20 feet/photo

Dwelling smoke alarms must produce an audible _____ signal for at least _____
minutes Correct Answer evacuation/ 4 minutes

Rechargeable power supplies for smoke alarms must recharge in _____ hours or less
when connected to a _____ portion of branch circuit Correct Answer 4/switched

smoke detectors must be installed within ______ feet of a door to a sleeping room
Correct Answer 21 feet

Wall mounted heat detectors must be mounted between _____ and _____ inches from
a ceiling Correct Answer 4''/12''

a fire alarm system must operate on standby for a period of not less than ______ days
followed by at least ______ minutes of alarm Correct Answer 7/4

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
ExamsGuru Grand Canyon University
View profile
Follow You need to be logged in order to follow users or courses
Sold
344
Member since
2 year
Number of followers
203
Documents
7694
Last sold
3 weeks ago
ExamsGuru

Before anything else, preparation is the key to success. We handle all kind of papers with accurate and complete solutions. Kindly send a direct message incase you miss what you are looking for since we will deliver within the shortest time possible. We respond as soon as possible and give guidance accordingly. Refer 3 of Your Friends and get a discount on 2 papers.

3.7

64 reviews

5
29
4
9
3
13
2
4
1
9

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions