1) no dwelling unit is supplied by more than one feeder
2) each dwelling unit is equipped with electric cooking equipment
(220.84(A)) - ANS-It shall be permissible to calculate the load of a feeder or services
that supplies three or more dwelling units of a multifamily dwelling in accordance with
Table 220.94 instead of Part III of this article if all ___________ is (are) met.
10 ft - ANS-Motor feeder tap conductors not over ______ long must have an ampacity
not less than one-tenth the rating of the feeder protection device:
100% NEC Code 215.2(A) Exp-2 - ANS-Feeder neutral or grounded conductors of
voltage rating not more than 600V, that do not connect to the terminals of an over
current protective device shall be sized based on ______ of the continuous load and
noncontinuous load
12 ft - ANS-If multiple power sources supply portable structures, the circuit equipment
grounding conductors at each portable structures must be bonded together for all
portable structures separated by less than ____:
1200 amps NEC Code 230.95(A) - ANS-The maximum setting for ground-fault
protection system regarding service over current protection is ____:
5% - ANS-According to NEC Code, reasonable efficiency can be achieved if the total
sum of voltage drop of branch circuit plus feeder is within ______ of the rated voltage
50 ft NEC Code 400.14 - ANS-In industrial establishments where the conditions of
maintenance and supervision ensure that only qualified persons will service the
installation, flexible cords or flexible cables not exceeding _____ can be installed in
aboveground raceways:
6 AWG, 8AWG (230.202) - ANS-Service-entrance conductors tp buildings or enclosure
shall be installed shall not be smaller than ________ AWG unless in multiconductor
cable. Multiconductor cable shall not be smaller than _______ AWG.
600 V - ANS-Qualified persons are permitted to carryout maintenance, monitoring and
servicing of the system which has voltage rating over _____ Volts
80% - ANS-Cord and plug equipment not fastened in place cannot be rated more than
______ of the branch circuit rating:
angle (348.42) - ANS-__________ connectors may not be concealed.
Ch. 2, Art. 250, Part VI Equipment Grounding and Equipment grounding conductor