THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE QUALIFICATIONS. - OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF __________ YEARS. - 3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH REQUIREMENTS. - IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S) ARE CONSIDERED PLANNED REMOV AL FROM SERVICE. - 1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS. - 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN ______ HOURS. - 8
FOR UNPLANNED REMOV AL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. - OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - 30
WHAT DOES "OOS" STAND FOR? - OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS, SYS. CONTROL V ALVES, AND FIRE COMMAND CENTER - TAGS A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL V ALVE AND ANY SECTIONAL V ALVES. - MASTER FIRE SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW PRESSURES BEFORE AND AFTER. - DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - NO IMPAIRMENT WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - MAIN CONTROL V ALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HA VE A ____________ TAG
PLACED ON THE MAIN CONTROL V ALVE. - RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE
THE SYSTEM IS PARTIALLY OUT OF SERVICE. - BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL STATION AND OCCUPANTS. - INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - 50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE ____________. - MAIN CONTROL V ALVE __________ SHALL BE READILY A V AILABLE TO ANY REPRESENTATIVE OF THE FIRE
DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT PROCEEDINGS. - REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD
THE FOLLOWING CERTS: - REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE OPERATING ENGINEER,
AND NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND SPRINKLER SYSTEMS. - MASTER FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS. - 30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN SPRINKLERS ARE INSTALLED. - 96
WET PIPE SYSTEMS HA VE WATER AT A MINIMUM TEMP. OF _______ TO PREVENT THE SYSTEM FROM FREEZING. - 40 FAHRENHEIT
__________ V ALVES ARE NO LONGER PERMITTED TO BE INSTALLED. - COLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE HEATED TO PREVENT FREEZING. - DRY PIPE
THE DROP IN ________ CAUSES A SPECIAL DRY PIPE V ALVE TO OPEN. - AIR PRESSURE
IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE ALARM IS TRANSMITTED DIRECTLY TO THE _________. - FIRE DEPARTMENT