Solutions
A by metallic heat detector. An example of. Correct Answers
Spot type detector.
A ceiling shall be treated as a smooth ceiling where the beams
project no more than how many inches. Correct Answers 4
inches.
A connection to a municipal fire alarm system to transmit an
alarm of fire to the municipal communications. Correct Answers
Auxiliary fire alarm.
A device used to terminate a supervised circuit. Correct Answers
End of the line.
A heat detector integrally mounted on a smoke detector shall be
listed or approved for not less than. Many feet. Correct Answers
50 feet.
A person with a fire alarm license may supervise how many
provisional certification personnel. Correct Answers One.
A provisional certificate issued authorizes an individual to
Correct Answers Be directly supervised by an individual who
possesses a valid and current certificate.
A signal indicating an emergency requiring immediate action is.
Correct Answers Alarm signal.
, a signalling method characterized by the simultaneous or
sequential transmission or b. and reception of multiple signals in
a communications channel. Is? Correct Answers Multiplexing.
A sloped ceiling is having a rise greater than. Correct Answers
One in 8.
A spot type detector located on a ceiling shall not be less than
how many inches from the side wall. The edge of the detector.
Correct Answers 4 inches.
A spot type heat detector located on a wall shall not be more
than how many inches from the ceiling. Correct Answers 12
inches.
A term usually applied to the simultaneous operation of. The
audible alarm signals on a system to indicate the need for
evacuation of a building is what? Correct Answers General
alarm.
A water flow devices shall be field adjusted so that an alarm is
initiated in no more than how many seconds. Correct Answers
90 seconds.
An alarm system which produces a signal at the premises
protected is a? Correct Answers Local protective signaling
system.
Auxiliary protective signaling systems are? Correct Answers
Tie into the municipal communications center.