S-12CITYWIDESPRINKLERSYSTEMS,S12
sprinkler test Spring 2023.
1. THE IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - answers>OWNER
2. RECORDS OFALL INSPECTIONS AND MX SHALL BEMAINTAINEDON PREMISES FOR A
MIN.OF
YEARS. - answers>3
3. THE BUILDING OWNER SHALL ASSIGN A(N) TO COMPLY WITH REQUIREMENTS.
-
answers>IMPAIRMENT COORDINATOR
4. REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN FLOOR(S)
ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - answers>1
5. SHUTDOWNS AFFECTINGMORE THAN FLOOR(S) ARE CONSIDERED UNPLANNED
OUT OF SERVICE CONDITIONS. - answers>1
6. NOTIFICATIONTOFDNYISNOTREQUIRED, PROVIDEDSYSTEM IS RETURNEDTOSERVICE
WITHIN
HOURS. - answers>8
7. FORUNPLANNEDREMOVALFROMSERVICE,THECOFHOLDERSHALLIMMEDIATELY
REPORT CONDITION TOTHE AND THE FIRE DEPT.- answers>OWNER OF THE
BUILDING
8. IFAMINORDEFECTISOBSERVED, ITSHALLBECORRECTEDWITHIN DAYSOR IT
WILL BE CONSIDERED AN IMPAIRMENT. -answers>30
9. WHATDOES "OOS" STANDFOR? - answers>OUT OF SERVICE
10. OOS SYSTEMS SHALL BE IDENTIFIED BY PLACINGAT FIRE DEPT. CONNECTIONS,
SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - answers>TAGS
, lOMoARcPSD|3013804
11. A SHALLBEREQUIREDTOPOSTTAGSATMAINCONTROLVALVEANDANY
SECTIONAL VALVES. - answers>MASTER FIRE SUPPRESSION PIPING
CONTRACTOR
12. SHALLBEPOSTEDONTHETAGINDICATINGBOTHSTATICANDFLOW
PRESSURES BEFORE AND AFTER. - answers>DRAIN TEST RESULTS
13. GREENTAGS INDICATETHAT . - answers>NO IMPAIRMENT WAS FOUND
14. GREENTAGSWILL BE PLACED ON THE . - answers>MAIN CONTROL VALVE
15. SYSTEMSPARTIALLYORFULLYOUTOFSERVICESHALLHAVEA TAGPLACED
ON THE MAIN CONTROL VALVE. - answers>RED
16. A DISCOF8-9INCHESSHALLBEPLACEDONCONNECTIONSTOINDICATETHE
SYSTEM IS FULLY OUT OF SERVICE. - answers>WHITE
17. A DISCOF8-9INCHESSHALLBEPLACEDONCONNECTIONSTOINDICATETHE
SYSTEM IS PARTIALLY OUT OF SERVICE. - answers>BLUE
18. THE IMPAIRMENT COORDINATOR WILL NOTIFY THE CARRIER, CENTRAL
STATION AND OCCUPANTS. -answers>INSURANCE
19. PRIORTORETURNINGASYS.TOSERVICE,THE SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. -answers>IMPAIRMENT
COORDINATOR
20. GLYCERINNOTGREATERTHAN PERCENT OR GLYCOL NOT GREATHER THAN
PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - answers>50, 40
21. THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
. - answers>MAIN CONTROL VALVE
, lOMoARcPSD|3013804
22. SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT.
THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - answers>RECORDS
23. FAILURETOMAKE INSPECTIONS MAYRESULTIN OFTHECOF AND
COURT PROCEEDINGS. - answers>REVOCATION
24. THE COF HOLDER MAYINSPECT,TEST,AND PERFORM ROUTINE MX IF THEY HOLD
THE FOLLOWING CERTS: - answers>REFRIGERATION OPERATING ENGINEER, HIGH
PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING
ENGINEER.
25. A CANINSPECT,MAINTAIN,TEST,ANDREPAIRALLFIRESTANDPIPEAND
SPRINKLER SYSTEMS. -answers>MASTER FIRE SUPPRESSION PIPING CONTRACTOR
(MFSPC)
26. A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH
SPRINKLER HEADS OR LESS. - answers>30
27. ABOUT PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN SPRINKLERS
ARE INSTALLED. - answers>96
28. WETPIPESYSTEMS HAVEWATERATAMINIMUM TEMP.OF TO PREVENT THE
SYSTEM FROM FREEZING. - answers>40FAHRENHEIT
29. VALVESARE NO LONGER PERMITTED TOBE INSTALLED.- answers>COLD
WEATHER
30. SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING. - answers>DRY PIPE
31. THE DROP IN CAUSES ASPECIAL DRYPIPE VALVETOOPEN. - answers>AIR PRESSURE
32. INBUILDINGSWHERELIFEHAZARDISHIGH(SCHOOLS,HOSPITALS)THEALARMIS
TRANSMITTED DIRECTLYTOTHE . - answers>FIRE DEPARTMENT
lOMoARcPSD|3013804
S-12CITYWIDESPRINKLERSYSTEMS,S12
sprinkler test Spring 2023.
1. THE IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - answers>OWNER
2. RECORDS OFALL INSPECTIONS AND MX SHALL BEMAINTAINEDON PREMISES FOR A
MIN.OF
YEARS. - answers>3
3. THE BUILDING OWNER SHALL ASSIGN A(N) TO COMPLY WITH REQUIREMENTS.
-
answers>IMPAIRMENT COORDINATOR
4. REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN FLOOR(S)
ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - answers>1
5. SHUTDOWNS AFFECTINGMORE THAN FLOOR(S) ARE CONSIDERED UNPLANNED
OUT OF SERVICE CONDITIONS. - answers>1
6. NOTIFICATIONTOFDNYISNOTREQUIRED, PROVIDEDSYSTEM IS RETURNEDTOSERVICE
WITHIN
HOURS. - answers>8
7. FORUNPLANNEDREMOVALFROMSERVICE,THECOFHOLDERSHALLIMMEDIATELY
REPORT CONDITION TOTHE AND THE FIRE DEPT.- answers>OWNER OF THE
BUILDING
8. IFAMINORDEFECTISOBSERVED, ITSHALLBECORRECTEDWITHIN DAYSOR IT
WILL BE CONSIDERED AN IMPAIRMENT. -answers>30
9. WHATDOES "OOS" STANDFOR? - answers>OUT OF SERVICE
10. OOS SYSTEMS SHALL BE IDENTIFIED BY PLACINGAT FIRE DEPT. CONNECTIONS,
SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - answers>TAGS
, lOMoARcPSD|3013804
11. A SHALLBEREQUIREDTOPOSTTAGSATMAINCONTROLVALVEANDANY
SECTIONAL VALVES. - answers>MASTER FIRE SUPPRESSION PIPING
CONTRACTOR
12. SHALLBEPOSTEDONTHETAGINDICATINGBOTHSTATICANDFLOW
PRESSURES BEFORE AND AFTER. - answers>DRAIN TEST RESULTS
13. GREENTAGS INDICATETHAT . - answers>NO IMPAIRMENT WAS FOUND
14. GREENTAGSWILL BE PLACED ON THE . - answers>MAIN CONTROL VALVE
15. SYSTEMSPARTIALLYORFULLYOUTOFSERVICESHALLHAVEA TAGPLACED
ON THE MAIN CONTROL VALVE. - answers>RED
16. A DISCOF8-9INCHESSHALLBEPLACEDONCONNECTIONSTOINDICATETHE
SYSTEM IS FULLY OUT OF SERVICE. - answers>WHITE
17. A DISCOF8-9INCHESSHALLBEPLACEDONCONNECTIONSTOINDICATETHE
SYSTEM IS PARTIALLY OUT OF SERVICE. - answers>BLUE
18. THE IMPAIRMENT COORDINATOR WILL NOTIFY THE CARRIER, CENTRAL
STATION AND OCCUPANTS. -answers>INSURANCE
19. PRIORTORETURNINGASYS.TOSERVICE,THE SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. -answers>IMPAIRMENT
COORDINATOR
20. GLYCERINNOTGREATERTHAN PERCENT OR GLYCOL NOT GREATHER THAN
PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - answers>50, 40
21. THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
. - answers>MAIN CONTROL VALVE
, lOMoARcPSD|3013804
22. SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT.
THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - answers>RECORDS
23. FAILURETOMAKE INSPECTIONS MAYRESULTIN OFTHECOF AND
COURT PROCEEDINGS. - answers>REVOCATION
24. THE COF HOLDER MAYINSPECT,TEST,AND PERFORM ROUTINE MX IF THEY HOLD
THE FOLLOWING CERTS: - answers>REFRIGERATION OPERATING ENGINEER, HIGH
PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING
ENGINEER.
25. A CANINSPECT,MAINTAIN,TEST,ANDREPAIRALLFIRESTANDPIPEAND
SPRINKLER SYSTEMS. -answers>MASTER FIRE SUPPRESSION PIPING CONTRACTOR
(MFSPC)
26. A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH
SPRINKLER HEADS OR LESS. - answers>30
27. ABOUT PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN SPRINKLERS
ARE INSTALLED. - answers>96
28. WETPIPESYSTEMS HAVEWATERATAMINIMUM TEMP.OF TO PREVENT THE
SYSTEM FROM FREEZING. - answers>40FAHRENHEIT
29. VALVESARE NO LONGER PERMITTED TOBE INSTALLED.- answers>COLD
WEATHER
30. SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING. - answers>DRY PIPE
31. THE DROP IN CAUSES ASPECIAL DRYPIPE VALVETOOPEN. - answers>AIR PRESSURE
32. INBUILDINGSWHERELIFEHAZARDISHIGH(SCHOOLS,HOSPITALS)THEALARMIS
TRANSMITTED DIRECTLYTOTHE . - answers>FIRE DEPARTMENT