With All Correct Answers Rated A+
Category 1 medical -surgical vacuum sources shall, at minimum, consist of ______ or
more vacuum pumps - Answer- Two
Category 1 medical surgical vacuum sources shall consist of an automatic means too
prevent _____ through any off -cycle vacuum pump - Answer- Backflow
Piping between the vacuum pump and the source shutoff valve shall be permitted to be
stainless, galvanized, or black steel pipe - Answer- True
Vacuum receiver shall be capable of withstanding a gauge vacuum of ______ of
mercury - Answer- 30"
The medical surgical vacuum receiver shall be made serviceable without shutting down
the system by _______ - Answer- Any method to ensure continuation service
When the medical surgical I'm an operation is incapable of adequately maintaining a
required vacuum, additional pump shall be _______ activated - Answer- Automatically
The medical surgical vacuum exhaust shall be turned down and screened. The
screened shall be fabricated using what type of material? - Answer- Any non-corroding
material
Multiple vacuum pumps shall be permitted to be join together to come one common
exhaust provided the common exhaust is size to ______. - Answer- Minimize back
pressure
Vacuum exhaust from multiple pumps join together to one common exhaust shall be
permitted provided each pump can be isolated by a _____. - Answer- Blind flange,
manual valve, check valve
Category 1 medical-surgical vacuum systems shall activate which alarm when the
backup or lag pump is running? - Answer- Local
A level 1 dedicated WAGD source shall consist of ______ or more producers, each
shall be sufficient to serve the peak calculated demand. - Answer- Two
What source shall not be used to power the venturi of a WAGD system? - Answer-
Medical air
, WAGD vacuum producers designed for operation at vacuums below ____ Hg/V shall be
used only for WAGD service and not employed for other services. - Answer- 5"
A WAGD source system shall activate the ____ alarm when the backup or lag producer
is running. - Answer- Local
Additional WAGD producers shall be ________ activated when the producer(s) in
operation is incapable of maintaining required vacuum. - Answer- Automatically
Medical air supply systems shall be required to _____. - Answer- Meet the requirements
of medical air USP, have no detectable liquid hydrocarbons, have less than 25 ppm
gaseous hydrocarbons
Medical air sources shall be used only for _____. - Answer- Human respiratory
applications
Medical air compressor systems shall have a(n) ______ means to prevent back flow
through all off-cycle compressors - Answer- Automatic
True - Answer- An existing system that is not in strict compliance with the provisions of
this standard shall be permitted to be continued in use as long as the authority having
jurisdiction has determined that such use does not constitute a distinct hazard to life
True - Answer- Cylinder and cryogenic liquid container outlet connections shall be
designed as to render the attachment point unusable when removal of the outlet
connection is attempted
Medical air sources - Answer- Which of the following systems shall not be permitted to
be located in an indoor enclosure
Engines, kitchens, and anesthizing locations - Answer- Indoor locations for oxygen,
nitrous oxide and mixtures of these gases shall not communicate with ______ locations.
130 degree F - Answer- Cylinders in use and in storage shall be prevented from
reaching temperatures in excess of ______.
True - Answer- Locations for central supply systems shall have electrical devices
protected from physical damage.
True - Answer- Ventilation requirements shall not be less than 50 cfm for mechanical
ventilation.
72 sq. in. - Answer- Louvered openings for natural ventilation shall have a minimum free
area of _____.