LP Gas Master Qualifier: Dispensing Installation & Maintenance
Questions and Answers with Solutions
The point of transfer at a dispensing unit must be ____ from
Public ways, including public streets, highways, thoroughfares,
and sidewalks.
A. 10 feet
B. 15 feet
C. 25 feet - ANSWER A. 10 feet
Steel supports on vertical ASME containers shall be protected
against fire exposure with a material having a fire resistance
rating of a least _____, except that continuous steel skirts that
have only one opening that is 18 in. or less in diameter shall
have fire protection applied to the ______ of the skirts.
A. 3 hrs; outside
B. 2 hrs; outside
C. 3 hrs; inside - ANSWER B. 2 hrs; outside
, 2|Page
Pressure relief devices installed in underground containers
serving dispensing systems shall be piped vertically upward to a
point at least _____ above the ground.
A. 2 feet
B. 6 feet
C. 10 feet - ANSWER C. 10 feet
A remote emergency shut off device for either the internal
valve or emergency shutoff valve is required to be located not
less than _____ or more than _____ from the liquid transfer
point.
A. 10 ft ; 50ft
B. 10 ft; 100ft
C. 3 ft; 100ft - ANSWER C. 3 ft; 100ft
The markings for the switch or circuit breaker to shut off power
in an emergency shall be visible from ________.
A. The front entrance to the business