GRADED A+ LATEST UPDATE.
How long does an owner have to fix a significant violation that does not pose an
imminent threat to human health and safety or environment before being issued
a red tag?
a) 24 hours
b) 48 hours
c) 7 days
d) 30 days ANS >>> c) 7 days; CCR 2717.1(b)
Which one of the following can perform ELD?
a) licensed tank tester
b) licensed state contractor
c) ICC certified service technician
d) Professional Engineer ANS >>> a) licensed tank tester; CCR2644.1 and 2643(f);
HSC 25484.4
Which one contains the requirements for installing, repairing, and monitoring
USTs?
a) Health and Safety Code Chapter 6.7
, b) Fire Code ABCD
c) California Code of Regulations Chapter 16, Title 22
d) Code of Federal Regulations, 29 Chapter 6 ANS >>> a) HSC Chapter 6.7 and CCR
Title 23
A monitoring system certification includes all of the following EXCEPT
a) submittal of a completed Monitoring System Certification form
b) pre-notification to the local agency of scheduled Monitoring System
Certification date
c) affixing a tag/sticker to each monitoring equipment component that is certified,
repaired, or replaced
d) posting the Monitoring System Certification from a visible location at the UST
facility ANS >>> d) posting the Monitoring System Certification from a visible
location at the UST facility; CCR 2638
Which of the following is not a valid overfill prevention method?
a) Spill bucket
b) ATG with audible/visual alarm
c) Ball float valve
d) Flapper valve ANS >>> a) Spill bucket; CCR 2635(b)(2)
What is the purpose of interstitial monitoring?
a) to detect leaks in the DC’s
b) to detect the presence of fluid between the primary and secondary
containment
c) to monitor tank volume