Conduit protecting gas piping installed underneath a building shall extend
not less than __________ beyond the point where the pipe emerges from the floor. - Answers 2
Galvanizing shall be considered adequate protection for __________ piping. - Answers Exposed
exterior
The test pressure for gas distribution pressures up to ½ psi is __________ psig for __________
minutes. - Answers 3; 30
The testing pressure for gas distribution pressures over ½ psig through 5 psig is __________ psig
for __________ minutes. - Answers 50; 30
The testing pressure for gas distribution pressures over 5 psig through 15 psig is __________
psig for __________ hour(s). - Answers 100; 1
The testing pressure for gas distribution pressures over 15 psig is __________
times the maximum operating pressure but not less than __________ psig for ___________ hours -
Answers 2... 100... 1
For gas distribution pressures requiring test pressures over 125 psig, the test
pressure shall not exceed a value that produces a hoop stress greater than
__________ % of the minimum yield strength. - Answers 50
Gas meter piping shall be pressure tested as per the __________. - Answers Utility
Where a single meter is used to supply gas to more than one
building/tenant, a separate __________ shall be provided for each
building/tenant. - Answers Shutoff valve
Coated and wrapped gas piping shall be tested with no less than __________ psig - Answers 90
Fresh water may be used as a testing medium for gas piping when testing at
pressures over __________ psig. - Answers 100
All nonmercury gauges measuring pressures in the magnitude of 3 psig shall
have faces not smaller than __________ inches diameter. - Answers 2 1/4
To protect an analog gauge from excessive test pressures, a tire gage shall be