Does a fire hood system and a kitchen need to be monitored by the fire
alarm system? - answer--Yes
What does P.L.F.A stand for? - answer--Power Limited Fire Alarm
What does N.P.L.F.A stand for? - answer--Non-Power Limited Fire Alarm
What is the difference between P.F.L.A and N.P.F.L.A? - answer--an
N.P.L.F.A can operate at up to 600v, and the power output isn't limited
a P.L.F.A has the voltage and power limited by a listed power source.
What material must N.P.F.L.A circuit conductors be made from? -
answer--ONLY solid stranded copper is permitted.
What does A.W.G stand for? - answer--American Wire Gauge
,What size conductors are permitted? - answer--Size 18 A.W.G and 16
A.W.G are permitted, provided they do not exceed certain capacities.
What is used to protect transformers or other devices supplied from
power-supply conductors? - answer--An over-current device not rated
over 20 amperes.
When located within 7 feet of the floor, how shall cables be fastened? -
answer--Cables shall be fastened in an approved manner at intervals of
not more than 18 inches.
Single conductors shall not be smaller than ___ A.W.G? - answer--18
Conductors of 28 A.W.G shall only be permitted in which circumstance?
- answer--Spliced with a connector listed as suitable for 26 to 24 A.W.G
How shall P.F.L.A conductors NOT be installed? - answer--P.F.L.A
conductors shall not be strapped, taped, or attached to the exterior of
any conduit or raceway.
What is Plenum cable? - answer--Cable that can be installed in ducts,
plenums, or other spaces used for environmental air.
, What is a Riser cable? - answer--Cable to be used in vertical wire runs in
shafts between floors. Not to be used where Plenum cable is required.
It is capable of preventing fire from rising from floor to floor.
What is general purpose cable? - answer--Cable for general purpose fire
alarm use. Not to be used where plenum cable or riser cable is
required.
It is resistant to the spread of fire.
Why 'type' shall plenum cable be? What substitutions are allowed? -
answer--Power Limited Fire Alarm Plenum (F.P.L.P) C.M.P can be
substituted.
Why 'type' shall riser cable be? What substitutions are allowed? -
answer--Power Limited Fire Alarm Riser (F.P.L.R) C.M.P, F.P.L.P.
C.M.R can be substituted.
What 'type' shall general purpose wire be? What substitutions are
permitted? - answer--Power Limited Fire Alarm (F.P.L) C.M.P, F.P.L.P,
C.M.R, F.P.L.R, C.M.G
solved & updated 2025-2026(latest version verified
for accuracy)
Does a fire hood system and a kitchen need to be monitored by the fire
alarm system? - answer--Yes
What does P.L.F.A stand for? - answer--Power Limited Fire Alarm
What does N.P.L.F.A stand for? - answer--Non-Power Limited Fire Alarm
What is the difference between P.F.L.A and N.P.F.L.A? - answer--an
N.P.L.F.A can operate at up to 600v, and the power output isn't limited
a P.L.F.A has the voltage and power limited by a listed power source.
What material must N.P.F.L.A circuit conductors be made from? -
answer--ONLY solid stranded copper is permitted.
What does A.W.G stand for? - answer--American Wire Gauge
,What size conductors are permitted? - answer--Size 18 A.W.G and 16
A.W.G are permitted, provided they do not exceed certain capacities.
What is used to protect transformers or other devices supplied from
power-supply conductors? - answer--An over-current device not rated
over 20 amperes.
When located within 7 feet of the floor, how shall cables be fastened? -
answer--Cables shall be fastened in an approved manner at intervals of
not more than 18 inches.
Single conductors shall not be smaller than ___ A.W.G? - answer--18
Conductors of 28 A.W.G shall only be permitted in which circumstance?
- answer--Spliced with a connector listed as suitable for 26 to 24 A.W.G
How shall P.F.L.A conductors NOT be installed? - answer--P.F.L.A
conductors shall not be strapped, taped, or attached to the exterior of
any conduit or raceway.
What is Plenum cable? - answer--Cable that can be installed in ducts,
plenums, or other spaces used for environmental air.
, What is a Riser cable? - answer--Cable to be used in vertical wire runs in
shafts between floors. Not to be used where Plenum cable is required.
It is capable of preventing fire from rising from floor to floor.
What is general purpose cable? - answer--Cable for general purpose fire
alarm use. Not to be used where plenum cable or riser cable is
required.
It is resistant to the spread of fire.
Why 'type' shall plenum cable be? What substitutions are allowed? -
answer--Power Limited Fire Alarm Plenum (F.P.L.P) C.M.P can be
substituted.
Why 'type' shall riser cable be? What substitutions are allowed? -
answer--Power Limited Fire Alarm Riser (F.P.L.R) C.M.P, F.P.L.P.
C.M.R can be substituted.
What 'type' shall general purpose wire be? What substitutions are
permitted? - answer--Power Limited Fire Alarm (F.P.L) C.M.P, F.P.L.P,
C.M.R, F.P.L.R, C.M.G