Med Gas Exam Questions With Reviewed 100% Correct Detailed Answers Guaranteed Pass!!Current Update In a Category 1 Dental and Gas Vacuum Piping system, which of the following is an NFPA 99 requirement for the labeling of pipes? - Answer- Color coding & non-standard pressure Which of the following treatments shall be performed before brazing cut ends of a tube to be installed in a medical gas piping system? - Answer- Cut ends shall be rolled smooth or deburred Manifolds for gas cylinders shall actuate a(an) _______ signal and shall activate an indicator at all _______ alarm panels to indicate when or just before changeover from one header to the other. - Answer- Local, master When is the initial pressure test conducted, by a medical gas installer, on a nitrous oxide system? - Answer- After blowdown of a distribution piping In those portions of systems intended to handle oxygen at pressures greater than 350 psi the interconnecting hose shall NOT contain ________ materials? - Answer- Polymeric In a non-anesthetizing area, on which side of a zone valve shall the pressure/vacuum sensor be located? - Answer- Station outlet/inlet What is the purpose of using an oxygen analyzer during the piping purge prior to brazing? - Answer- Assure that all ambient air has been removed from the pipeline A medical gas master or area alarm panel shall be set to actuate a(an) _____ indicator when the communication with an alarm-initiating device is disconnected. - Answer- Audible and visual When an EOSC becomes the temporary supply source, a facility will monitor the system by use of which of the following? - Answer- Providing four connection points to both master alarms Which of the following conditions must be met where medical gas and vacuum systems are installed by non-certified personnel? - Answer- installation by anyone other than 6010 certified personnel is NOT permitted Which of the following systems shall NOT be permitted to be located in an outdoor enclosure? - Answer- Medical air compressor supply sources Metallic flexible joints are being used in the pipeline for vibration control. Which of the following is NOT required of such joints? - Answer- suitable for service at 150 psig or above who shall witness the installer-performed standing vacuum test? - Answer- the authority having jurisdiction, or its designee the medical air compressor intake shall be located a minimum of how many feet from any exhaust or plumbing vents? - Answer- 25 feet the gas produced by evaporation from the secondary header in a cryogenic liquid cylinder system shall enter the supply system ________ of the final line regulator. - Answer- upstream with the approval of the Authority Having Jurisdiction, in which areas shall the zone valves be permitted to be secured to prevent inappropriate access? - Answer- pediatric factory installed inlet tubes on station outlets shall be NOT less than __________with 0.3 inch minimum inside diameter. - Answer- NPS 1/4, 3/8 in. O.D. which of these operations would not breach the vacuum system? - Answer- testing a system component with a leak detector solution except for valves in zone valve boxes, all valves shall be located in secured areas such as locked pipe chases, or be __________. - Answer- latched or locked in operation position medical gas Central Supply systems are NOT permitted to be located where? - Answer- in an unlocked location fittings, valves, and other components for field-installed positive pressure distribution systems shall be ________ until prepared for installation. - Answer- delivered sealed, labeled, and kept sealed vacuum piping for __________ shall be connected separately from the medical surgical system directly to the receiver tank through its own isolation valve and fluid trap located at the receiver. - Answer- a teaching laboratory NFPA 99 specifies that the medical gas piping system shall be protected against all EXCEPT which of the following? - Answer- exposure to liquids category 1 support gasses carry which of these additional hazards? - Answer- higher pressures manufactured assemblies for medical gas systems employing flexible hose shall use flexible connectors with a minimum burst gauge pressure of how many psi? - Answer- 1000 an assembly of equipment that holds a capacity of oxygen greater than ____________ is defined as a Bulk Oxygen System - Answer- 20,000 ft^3 what does it mean when equipment, material or services are shows as "listed"? - Answer- they are identified and published by an organization that is acceptable to the authority having jurisdiction under which of these conditions shall instrument air reserve header cylinders be permitted to be stored with the instrument air compressor? - Answer- the only motor-driven machinery in the rooms is for the instrument air equipment. which type of copper tube hangers shall be used in a potentially damp location? - Answer- plastic coated stainless tubes may be joined by any methods EXCEPT which of the following? - Answer- Braze gas storage for Central Supply Systems required specialized knowledge and consideration of information in the NFPA 55 for locating, installing and inspection of which of the following? - Answer- Bulk Gas all pressure relief valves shall be made of ______ brass, or bronze. - Answer- stainless steel the reserve header in a cryogenic liquid cylinder manifold system shall have sufficient cylinder connections for one average day's supply, but NOT fewer than how many connections? - Answer- 3 all fittings for medical gas work shall be kept separate from other tools and kept free of grease or oil. If cleaned, only a degreaser such as __________ is permitted. - Answer- trisodium phosphate or sodium carbonate with potable water station outlets/inlets shall be identified as to the ________ for the specific gas or vacuum provided. - Answer- name or chemical symbol when brazing, joints shall be continuously purges with oil-free, dry nitrogen NF to prevent the formation of __________ on the inside surfaces of the joint. - Answer- copper oxide a bulk cryogenic supply contains parallel-piped duplex line regulators. Which of the following is a requirement for controls for line pressure? - Answer- a balanced design

Show more Read less
Institution
Med Gas
Course
Med Gas

Content preview

Med Gas Exam Questions With
Reviewed 100% Correct Detailed
Answers Guaranteed Pass!!Current
Update
In a Category 1 Dental and Gas Vacuum Piping system, which of the following is an
NFPA 99 requirement for the labeling of pipes? - Answer- Color coding & non-standard
pressure

Which of the following treatments shall be performed before brazing cut ends of a tube
to be installed in a medical gas piping system? - Answer- Cut ends shall be rolled
smooth or deburred

Manifolds for gas cylinders shall actuate a(an) _______ signal and shall activate an
indicator at all _______ alarm panels to indicate when or just before changeover from
one header to the other. - Answer- Local, master

When is the initial pressure test conducted, by a medical gas installer, on a nitrous
oxide system? - Answer- After blowdown of a distribution piping

In those portions of systems intended to handle oxygen at pressures greater than 350
psi the interconnecting hose shall NOT contain ________ materials? - Answer-
Polymeric

In a non-anesthetizing area, on which side of a zone valve shall the pressure/vacuum
sensor be located? - Answer- Station outlet/inlet

What is the purpose of using an oxygen analyzer during the piping purge prior to
brazing? - Answer- Assure that all ambient air has been removed from the pipeline

A medical gas master or area alarm panel shall be set to actuate a(an) _____ indicator
when the communication with an alarm-initiating device is disconnected. - Answer-
Audible and visual

When an EOSC becomes the temporary supply source, a facility will monitor the system
by use of which of the following? - Answer- Providing four connection points to both
master alarms

Which of the following conditions must be met where medical gas and vacuum systems
are installed by non-certified personnel? - Answer- installation by anyone other than
6010 certified personnel is NOT permitted

,Which of the following systems shall NOT be permitted to be located in an outdoor
enclosure? - Answer- Medical air compressor supply sources

Metallic flexible joints are being used in the pipeline for vibration control. Which of the
following is NOT required of such joints? - Answer- suitable for service at 150 psig or
above

who shall witness the installer-performed standing vacuum test? - Answer- the authority
having jurisdiction, or its designee

the medical air compressor intake shall be located a minimum of how many feet from
any exhaust or plumbing vents? - Answer- 25 feet

the gas produced by evaporation from the secondary header in a cryogenic liquid
cylinder system shall enter the supply system ________ of the final line regulator. -
Answer- upstream

with the approval of the Authority Having Jurisdiction, in which areas shall the zone
valves be permitted to be secured to prevent inappropriate access? - Answer- pediatric

factory installed inlet tubes on station outlets shall be NOT less than __________with
0.3 inch minimum inside diameter. - Answer- NPS 1/4, 3/8 in. O.D.

which of these operations would not breach the vacuum system? - Answer- testing a
system component with a leak detector solution

except for valves in zone valve boxes, all valves shall be located in secured areas such
as locked pipe chases, or be __________. - Answer- latched or locked in operation
position

medical gas Central Supply systems are NOT permitted to be located where? - Answer-
in an unlocked location

fittings, valves, and other components for field-installed positive pressure distribution
systems shall be ________ until prepared for installation. - Answer- delivered sealed,
labeled, and kept sealed

vacuum piping for __________ shall be connected separately from the medical surgical
system directly to the receiver tank through its own isolation valve and fluid trap located
at the receiver. - Answer- a teaching laboratory

NFPA 99 specifies that the medical gas piping system shall be protected against all
EXCEPT which of the following? - Answer- exposure to liquids

category 1 support gasses carry which of these additional hazards? - Answer- higher
pressures

, manufactured assemblies for medical gas systems employing flexible hose shall use
flexible connectors with a minimum burst gauge pressure of how many psi? - Answer-
1000

an assembly of equipment that holds a capacity of oxygen greater than ____________
is defined as a Bulk Oxygen System - Answer- 20,000 ft^3

what does it mean when equipment, material or services are shows as "listed"? -
Answer- they are identified and published by an organization that is acceptable to the
authority having jurisdiction

under which of these conditions shall instrument air reserve header cylinders be
permitted to be stored with the instrument air compressor? - Answer- the only motor-
driven machinery in the rooms is for the instrument air equipment.

which type of copper tube hangers shall be used in a potentially damp location? -
Answer- plastic coated

stainless tubes may be joined by any methods EXCEPT which of the following? -
Answer- Braze

gas storage for Central Supply Systems required specialized knowledge and
consideration of information in the NFPA 55 for locating, installing and inspection of
which of the following? - Answer- Bulk Gas

all pressure relief valves shall be made of ______ brass, or bronze. - Answer- stainless
steel

the reserve header in a cryogenic liquid cylinder manifold system shall have sufficient
cylinder connections for one average day's supply, but NOT fewer than how many
connections? - Answer- 3

all fittings for medical gas work shall be kept separate from other tools and kept free of
grease or oil. If cleaned, only a degreaser such as __________ is permitted. - Answer-
trisodium phosphate or sodium carbonate with potable water

station outlets/inlets shall be identified as to the ________ for the specific gas or
vacuum provided. - Answer- name or chemical symbol

when brazing, joints shall be continuously purges with oil-free, dry nitrogen NF to
prevent the formation of __________ on the inside surfaces of the joint. - Answer-
copper oxide

a bulk cryogenic supply contains parallel-piped duplex line regulators. Which of the
following is a requirement for controls for line pressure? - Answer- a balanced design

Written for

Institution
Med Gas
Course
Med Gas

Document information

Uploaded on
September 25, 2025
Number of pages
20
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

$22.29
Get access to the full document:

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
Stuviaascorers University of Washington
View profile
Follow You need to be logged in order to follow users or courses
Sold
375
Member since
3 year
Number of followers
185
Documents
11059
Last sold
1 day ago
StuviaAscorers | Top Study Notes & Exam Solutions

Stuviaascorers – Your #1 Source for Top-Quality Study Materials! Struggling with exams? Stuviaascorers has got you covered! I provide expertly crafted study notes, summaries, past papers, and exam-ready answers to help you pass with flying colors. My materials are designed for clarity, accuracy, and success—so you can study smarter, not harder! Why Choose My Study Materials? Well-structured & easy to understand – No fluff, just what you need! Exam-focused & high-scoring content – Get straight to the point! Accurate answers & clear explanations – Learn with confidence! Save time & boost your grades – Study efficiently! Don’t leave your success to chance! Browse my documents and start acing your exams today!

Read more Read less
3.7

67 reviews

5
31
4
11
3
12
2
2
1
11

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions