NETA LEVEL 2 EXAM WITH CORRECT
DETAILED ANSWERS
Two capacitors, a 20 µF and a 30 µF, are connected in parallel to a 400 Hz source.
The total capacitive reactance is
a) 7.96 ohms
b) 33.16 ohms
c) 221.04 ohms
d) 53.05 ohms -correct-answer-Answer: a) 7.96 ohms
The formula for calculating capacitive reactance is XC = 1/(2πfC), where:
XC: is the capacitive reactance, measured in ohms
f: is the frequency of the alternating current in hertz
C: is the capacitance of the capacitor in farads
The total reactance of capacitors connected in series can be calculated using the
equation XCT = XC1 + XC2 + XC3 + ... + XCN
Place the hierarchy of backup power systems to the order in which they appear in
the NEC.
a. Legally required standby systems
b. Emergency power systems
c. Optional standby systems -correct-answer-Answer: b, a, c
NFPA NEC
,2|Page
In rotating machines, how can electromagnetic test methods be used to assess the
interlaminar insulation in the stator core?
a) By measuring the machine's efficiency
b) By detecting excessive local heating
c) By analyzing the circulating currents
d) By inspecting the visual condition of the laminations -correct-answer-Answer:
c) By analyzing the circulating currents
Why is it important to note the equipment load conditions during an infrared
inspection?
a) To adjust the temperature scale on the thermal imager
b) To identify areas of thermal reflection
c) To determine the severity of a problem
d) To ensure the equipment is not overloaded -correct-answer-Answer: c) to
determine the severity of the problem
Fiber jumpers (also called patch cords) usually have ____ fiber(s).
a) 1
b) 2
c) 3
,3|Page
d) 4 -correct-answer-Answer: b) 2
Before confined space entry begins, the entry supervisor listed on the permit shall
sign what?
a) Procedures for summoning rescue and emergency services
b) The entry permit to authorize entry
c) Atmospheric tests
d) List of persons who are to have active roles
e) Permit concluding the entry -correct-answer-Answer: b) the entry permit to
authorize entry
Help: OSHA 1910.146(e)(2)
When multiple auxiliary rod, pipe, or plate electrodes are installed for providing a
grounding system, they shall not be less than _____ apart.
a) 8 feet
b) 5 feet
c) 6 feet
d) 10 feet -correct-answer-Answer: c) 6 feet
Help NFPA NEC
After connection of test equipment is complete, you should next:
, 4|Page
a) Power on the test equipment
b) Warn others in the area that testing has started
c) Recheck test equipment connections and settings
d) Create a no-entry zone for unqualified personnel
e) Take a break -correct-answer-Answer: c) Recheck test equipment connections
and settings.
In accordance with NFPA-70E, a balaclava is required:
a) When working on energized equipment
b) When wearing an arc-flash hood
c) When wearing a face shield
d) When the rear of the head is inside the arc flash boundary -correct-answer-
Answer: d) when the rear of the head is inside the flash boundary.
Help: NFPA 70E-2024 Table 130.5 (G)
According to NETA Acceptance Testing Specifications, what is the maximum
acceptance power factor at 25 degrees Celsius for new mineral oil to be used in
new equipment rated 69KV and below?
a) 0.15%
b) 0.40%
c) 1.0%
d) 0.05%