Class D hazard fire extinguisher travel distance? --- correct precise
answer ---75 ft
Class K hazard maximum travel distance? --- correct precise answer --
-30 ft
Who is responsible for inspections, maintenance and recharging of
fire extinguishers? --- correct precise answer ---Owner or designated
agent
Which 4 parts are examined during maintence? --- correct precise
answer ---Mechanical parts, extinguishing agent, expelling means,
physical condition
When examining a fire extinguisher, what two time-based
maintenance or testing is due? --- correct precise answer ---6 Year
and hydro testing
, When subjected to temperatures at or above rating, stored pressure
FE's must have what done? --- correct precise answer ---Emptied and
have applicable maintenance done
What type of extinguishing agent should be dissembled on a regular
basis and given complete maintenance? --- correct precise answer ---
Wetting agent
Pump tank extinguishers shall be internally examined how often? ---
correct precise answer ---Annually
What information should be on a service label? (6 year or hydro) ---
correct precise answer ---2x3.5 in waterproof label, month and year,
person performing work, name of agency performing work
How often are Co2 hoses supposed to be conductivity tested? ---
correct precise answer ---Yearly
If a conductivity test on a Co2 hose fails, what occurs? --- correct
precise answer ---Replacement