Medical Gas Assessment 1, 2 & 3 Exam
Questions and Answers
A ____ device is used for connecting the outlets of one or more gas cyclinders
to the central piping system? - -Manifold
- A factory assembled product designed for anesthetics or convenience that
contains medical gas outlets or vacuum inlets, piping, or other related to
medical gases is a ____ ? - -Manufactured assembly
- A warning system within an area uses a ____
that provides continuous visible and audible
surveillance of category 1 and category 2 medical gas and vacuum systems?
- -Area alarm
- Aftercoolers where required shall be provided with individual ____ ? - -
Condensate traps
- Carbon monoxide shall activate a local alarms when the CO level exceeds
____? - -10 ppm
- Compressors that are monitored for gases hydrocarbons shall be
monitored on a ____ basis - -Quarterly
- Filters shall be efficient to ____ and 99.7% HEPA or better per. DOE-STD-
3020 - -0.3
- Medical air shall be sampled at a ____ NPS valve sample port downstream
of the final line pressure regulator? - -1/4 inch
- The minimum clearance around the EOSC for a temporary sore is ____ feet?
- -3 feet
- The monitor shall be capable of monitoring ____ percent oxygen
concentration with one percent accuracy? - -99
- Within a single patient room or critical care area to provide access for two
or more gases through a common delivery system, which would be used? - -
Surface mounted medical gas rail system also known as MGR
- Which of the following systems shall not be permitted to be located in an
outdoor enclosure? - -medical air sources
, - What type of connection should be used to connect the medical air
compressors for a vacuum pumps to their intake an outlet piping? - -Flexible
- What is not part of a typical category one medical gas vacuum system? - -
Patient lead
- What is part of a typical category one medical gas vacuum system? - -An
inlet at locations where patient suction could be, pressure, gauges, and
operating controls, shut off valves
- What is a pneumatic terminous of a pipe gas system? Other than critical
continuous duty, non-flammable, medical gas life support type gases. - -
Service outlet
- What guide is for preparation of precautionary, labeling, and marketing of
compressed gas containers? - -CGA C-7
- Vacuum filtration shall be sized for ____ percent of the peak calculated
demand while one filter or filter bundle is isolated. - -100
- Vacuum filtration shall be at least ____ to allow one filter to be exchanged
without impairing the vacuum system? - -Duplex
- Louvered openings for natural ventilation shall have a minimum free area
of ____? - -72 square inches
- Medical air filters shall be located immediately upstream of the ____? - -
Final line regulators
- Cylinders and use an in storage shall be prevented reaching temperature is
an excess of ____? - -125 Fahrenheit
- All pressure relief valve shall be made of brass, bronze, or ____? - -
Stainless steel
- A category one dedicated WAGD source shall consist of ____ or more
producers, each shall be sufficient to serve the peak calculated demand - -2
- A variant on the cryogenic liquid container manifold shall be permitted to
have three headers. Such a variant shall have a minimum of ____
connections required for each of the primary and secondary headers. - -2
- For each oxygen concentrator a local alarm to indicate low oxygen
concentration when a concentration lower than ____ percent is observed? - -
91
Questions and Answers
A ____ device is used for connecting the outlets of one or more gas cyclinders
to the central piping system? - -Manifold
- A factory assembled product designed for anesthetics or convenience that
contains medical gas outlets or vacuum inlets, piping, or other related to
medical gases is a ____ ? - -Manufactured assembly
- A warning system within an area uses a ____
that provides continuous visible and audible
surveillance of category 1 and category 2 medical gas and vacuum systems?
- -Area alarm
- Aftercoolers where required shall be provided with individual ____ ? - -
Condensate traps
- Carbon monoxide shall activate a local alarms when the CO level exceeds
____? - -10 ppm
- Compressors that are monitored for gases hydrocarbons shall be
monitored on a ____ basis - -Quarterly
- Filters shall be efficient to ____ and 99.7% HEPA or better per. DOE-STD-
3020 - -0.3
- Medical air shall be sampled at a ____ NPS valve sample port downstream
of the final line pressure regulator? - -1/4 inch
- The minimum clearance around the EOSC for a temporary sore is ____ feet?
- -3 feet
- The monitor shall be capable of monitoring ____ percent oxygen
concentration with one percent accuracy? - -99
- Within a single patient room or critical care area to provide access for two
or more gases through a common delivery system, which would be used? - -
Surface mounted medical gas rail system also known as MGR
- Which of the following systems shall not be permitted to be located in an
outdoor enclosure? - -medical air sources
, - What type of connection should be used to connect the medical air
compressors for a vacuum pumps to their intake an outlet piping? - -Flexible
- What is not part of a typical category one medical gas vacuum system? - -
Patient lead
- What is part of a typical category one medical gas vacuum system? - -An
inlet at locations where patient suction could be, pressure, gauges, and
operating controls, shut off valves
- What is a pneumatic terminous of a pipe gas system? Other than critical
continuous duty, non-flammable, medical gas life support type gases. - -
Service outlet
- What guide is for preparation of precautionary, labeling, and marketing of
compressed gas containers? - -CGA C-7
- Vacuum filtration shall be sized for ____ percent of the peak calculated
demand while one filter or filter bundle is isolated. - -100
- Vacuum filtration shall be at least ____ to allow one filter to be exchanged
without impairing the vacuum system? - -Duplex
- Louvered openings for natural ventilation shall have a minimum free area
of ____? - -72 square inches
- Medical air filters shall be located immediately upstream of the ____? - -
Final line regulators
- Cylinders and use an in storage shall be prevented reaching temperature is
an excess of ____? - -125 Fahrenheit
- All pressure relief valve shall be made of brass, bronze, or ____? - -
Stainless steel
- A category one dedicated WAGD source shall consist of ____ or more
producers, each shall be sufficient to serve the peak calculated demand - -2
- A variant on the cryogenic liquid container manifold shall be permitted to
have three headers. Such a variant shall have a minimum of ____
connections required for each of the primary and secondary headers. - -2
- For each oxygen concentrator a local alarm to indicate low oxygen
concentration when a concentration lower than ____ percent is observed? - -
91