When recovering refrigerant from a medium-pressure system with
more than 200 lbs. of refrigerant, recover to a level of;
Ans: 15" Hg
Refrigerant should be recovered from the condenser outlet if the
condenser is;
Ans: Below the receiver
A new split system should be checked for leaks by;
Ans: pressurizing the system with a few ounces of system refrigerant and
an inert gas.
Leaks must be repaired on industrial process and refrigeration units
with a 50-pound charge or greater when the annualized leak rate
reaches _____ or more.
, 2 | Page
Ans: 30%
Refrigerants CFC-12, HCFC-22, and HFC-134a are all classified as
Type _______ substances.
Ans: A1
A high-pressure appliance containing less than 200 lbs. of an HCFC
or HFC refrigerant must be evacuated (recovered) to a level of;
Ans: 0 inches of vacuum
When using a recovery unit on a system containing 100 lbs. of R-410A
it must be evacuated to;
Ans: 0 inches of Mercury
A refrigerant sensor which will sound an alarm and automatically
start a ventilation system in occupied equipment rooms falls under
ASHRAE Standard;