Answers (Graded A)
Max safety timing on a primary control - ANSWER-15 seconds
Safety control circuits shall be - ANSWER-2-wire, one side grounded, with
nominal voltage not exceeding 150v
Crankcase/used oil may only be used in - ANSWER-Commercial/industrial
setting. Or in a appliance specifically designed to do so.
What must I do if I have a tank larger than 10,000 gallons? - ANSWER-You
must apply for, and obtain both a permit and a license from the local town or
city for the use of the tank and the storage of the fuel oil.
What licenses are acceptable for installing an oil burner and or an oil tank? -
ANSWER-Holder of certificate of competency
, Can anyone make out Form 1 or Form 1A? - ANSWER-Yes, but only a holder
of a Certificate of Competency can sign as the installer on a Form 1 and as
the inspector in the case of a Form 1A.
Oil burning appliance shall be how far from electrical panel and oil tank -
ANSWER-3 feet from panel, 5 feet from tank
Natural draft chimney connector shall not exceed __ unless a draft fan is
used - ANSWER-10 feet
A chimney connector shall not pass through a - ANSWER-Floor or cieling
Chimney connector of low, medium, or high heat Industrial appliance shall
not pass through a - ANSWER-Combustible wall of partisan
Chimney connector need a pitch of - ANSWER-1/4
A venting system that terminates in the sidewall shall be - ANSWER-3 feet
above any air inlet that is within 10 feet of the vent.