Refer to the information shown in Figure 234.151. When the tap for Motor 3 terminates in a safety switch, the maximum permitted size for DETD fuses in this switch would be _____ A. -answer- 15 Refer to the information shown in Figure 234.151. When the tap for Motor 1 terminates in a breaker enclosure, the maximum permitted size for an ITCB in this enclosure would be ____ A. -answer- 70 Refer to the information shown in Figure 234.151. When th etap for Motor 3 terminates in a breaker enclosure, the maximum permitted size for an ITCB in this enclose would be ____ A. -answer- none of these Voltage Drop Scenario #3 The distance between the panel and a load is 150 feet. The circuit to the load consists of two 12 AWG solid copper coated conductors that are connected to a 1-pole breaker in a 277/480-volt, 3Ø, 4-wire panel and the neutral bar. The load draws 9.8 amps. Refer to Voltage Drop Scenario #3. If the voltage drop is to be limited to 2.2%, this is ___ volts. -answer- 6.09 Refer to Figure 221.404. The voltage applied to Heating Element B is ___ volts. -answer- 138.6 Refer to the nameplate and heater selection table, shown above in Figure 230.122. For a correctly sized starter, the heater catalog number for the heaters is ___. This motor is supplied power from a 120/240-volt, 3-phase, 4-wire panelboard. -answer- B32 Refer to the nameplate shown in Figure 230.122. The branch circuit for the motor is supplied from a 240/120-volt, 3Ø, 4-wire panelboard. What is the minimum size (3 wire + ground) SO cord that could be used as a flexible connection for the motor? -answer- 8 Refer to the nameplate shown in Figure 230.122. This motor should draw ___ amps at rated voltage when connected to Circuit 4-6-8 that is fed from a 3-pole breaker in a 120/240-volt, 3Ø, 4-wire panelboard. -answer- 18.6 Two lighting circuits are supplied from a multiwire branch circuit that originates in a 120/240 volt, 1Ø, 3-wire panelboard. Two, 20 Amp, 1-pole breakers are installed in spaces 22 & 24 for the multiwire circuit. Circuit 22 has 2600 watts of lights connected to it, and Circuit 24 has 2100 watts of lights connected to it. Which of the following should happen to Circuit 22? -answer- An overload will occur and the breaker will trip. Refer to Figure 221.402. If Ammeter 2 indicates 38.5 amps, the generator is delivering ___ kW of power. -answer- 16.0 The service disconnecting means for a 3-phase service is permitted to consist of ___. -answer- any of the above Nontime-delay fuses are to be installed in a safety switch adjacent to a motor. See Figure 230.225. Fuses with a rating not exceeding ___ A are permitted. -answer- 100 The classification of a location, where ignitable concentrations of flammable liquid-produced vapors or combustible liquid-produced vapors exist under normal operating conditions, is ___. -answer- Class I, Division 1 If a 4-wire, wye-connected supply system has a line-to-line voltage of 13.5 kV, what is the line-to-neutral voltage? -answer- 7,800 Refer to the motor nameplate shown in Figure 230.108. A NEMA starter will be used for this motor. The fewest number of heaters that can be installed in the starter per the NEC ® is ___. The motor circuit is supplied from a 2-pole breaker in a 120/240-volt, 3Ø, 4-W panel. -answer- 1 A transformer has a primary rated voltage of 120 and a secondary rated voltage of 16. If the current in the circuit conductors connected to the primary is 1.1 amps, the load that is connected to the secondary must be drawing ___ amps. -answer- 8.25 A set of wires (black, red, blue and green) are installed between a 3-pole safety switch and a 3Ø motor. The direction of rotation of the motor can be changed by swapping the ___ wire connections on the load side of the switch. -answer- black and blue ___ is permitted to be installed in a concrete floor slab. I. Schedule 40 PVC II. FMC III. aluminum MC cable -answer- I only A(n) ___ refrigerant motor-compressor is a combination compressor and motor in the same housing, having no external shaft or shaft seals, with the motor operating in the refrigerant. -answer- hermetic In a 60 Hz circuit, containing a 1.3 mh inductor, the inductive reactance is ___ ohms. -answer- .49 ___ is the measure of a circuit's ability to store an electrical charge. -answer- Capacitance

Show more Read less
Institution
IEC Year 2
Course
IEC year 2









Whoops! We can’t load your doc right now. Try again or contact support.

Written for

Institution
IEC year 2
Course
IEC year 2

Document information

Uploaded on
September 18, 2024
Number of pages
11
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

Content preview

IEC year 2 final exam review



IEC year 2 Final Exam Review 2024
Refer to the information shown in Figure 234.151. When the tap for Motor 3 terminates
in a safety switch, the maximum permitted size for DETD fuses in this switch would be
_____ A. -answer- ✔15

Refer to the information shown in Figure 234.151. When the tap for Motor 1 terminates
in a breaker enclosure, the maximum permitted size for an ITCB in this enclosure would
be ____ A. -answer- ✔70

Refer to the information shown in Figure 234.151. When th etap for Motor 3 terminates
in a breaker enclosure, the maximum permitted size for an ITCB in this enclose would
be ____ A. -answer- ✔none of these

Voltage Drop Scenario #3
The distance between the panel and a load is 150 feet. The circuit to the load consists
of two 12 AWG solid copper coated conductors that are connected to a 1-pole breaker
in a 277/480-volt, 3Ø, 4-wire panel and the neutral bar. The load draws 9.8 amps.

Refer to Voltage Drop Scenario #3. If the voltage drop is to be limited to 2.2%, this is
___ volts. -answer- ✔6.09

Refer to Figure 221.404. The voltage applied to Heating Element B is ___ volts. -
answer- ✔138.6

Refer to the nameplate and heater selection table, shown above in Figure 230.122. For
a correctly sized starter, the heater catalog number for the heaters is ___. This motor is
supplied power from a 120/240-volt, 3-phase, 4-wire panelboard. -answer- ✔B32

Refer to the nameplate shown in Figure 230.122. The branch circuit for the motor is
supplied from a 240/120-volt, 3Ø, 4-wire panelboard. What is the minimum size (3 wire
+ ground) SO cord that could be used as a flexible connection for the motor? -answer-
✔8

Refer to the nameplate shown in Figure 230.122. This motor should draw ___ amps at
rated voltage when connected to Circuit 4-6-8 that is fed from a 3-pole breaker in a
120/240-volt, 3Ø, 4-wire panelboard. -answer- ✔18.6

Two lighting circuits are supplied from a multiwire branch circuit that originates in a
120/240 volt, 1Ø, 3-wire panelboard. Two, 20 Amp, 1-pole breakers are installed in
spaces 22 & 24 for the multiwire circuit. Circuit 22 has 2600 watts of lights connected to
it, and Circuit 24 has 2100 watts of lights connected to it. Which of the following should
happen to Circuit 22? -answer- ✔An overload will occur and the breaker will trip.


IEC year 2 final exam review

, IEC year 2 final exam review


Refer to Figure 221.402. If Ammeter 2 indicates 38.5 amps, the generator is delivering
___ kW of power. -answer- ✔16.0

The service disconnecting means for a 3-phase service is permitted to consist of ___. -
answer- ✔any of the above

Nontime-delay fuses are to be installed in a safety switch adjacent to a motor. See
Figure 230.225. Fuses with a rating not exceeding ___ A are permitted. -answer- ✔100

The classification of a location, where ignitable concentrations of flammable liquid-
produced vapors or combustible liquid-produced vapors exist under normal operating
conditions, is ___. -answer- ✔Class I, Division 1

If a 4-wire, wye-connected supply system has a line-to-line voltage of 13.5 kV, what is
the line-to-neutral voltage? -answer- ✔7,800

Refer to the motor nameplate shown in Figure 230.108. A NEMA starter will be used for
this motor. The fewest number of heaters that can be installed in the starter per the
NEC ® is ___. The motor circuit is supplied from a 2-pole breaker in a 120/240-volt, 3Ø,
4-W panel. -answer- ✔1

A transformer has a primary rated voltage of 120 and a secondary rated voltage of 16. If
the current in the circuit conductors connected to the primary is 1.1 amps, the load that
is connected to the secondary must be drawing ___ amps. -answer- ✔8.25

A set of wires (black, red, blue and green) are installed between a 3-pole safety switch
and a 3Ø motor. The direction of rotation of the motor can be changed by swapping the
___ wire connections on the load side of the switch. -answer- ✔black and blue

___ is permitted to be installed in a concrete floor slab.
I. Schedule 40 PVC
II. FMC
III. aluminum MC cable -answer- ✔I only

A(n) ___ refrigerant motor-compressor is a combination compressor and motor in the
same housing, having no external shaft or shaft seals, with the motor operating in the
refrigerant. -answer- ✔hermetic

In a 60 Hz circuit, containing a 1.3 mh inductor, the inductive reactance is ___ ohms. -
answer- ✔.49

___ is the measure of a circuit's ability to store an electrical charge. -answer-
✔Capacitance



IEC year 2 final exam review

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
PossibleA Chamberlain College Of Nursing
View profile
Follow You need to be logged in order to follow users or courses
Sold
992
Member since
4 year
Number of followers
650
Documents
12812
Last sold
3 days ago
POSSIBLEA QUALITY UPDATED EXAMS

Choose quality study materials for nursing schools to ensure success in your studies and future career. "Welcome to PossibleA - your perfect study assistant! Here you will find Quality sheets, study materials, exams, quizzes, tests, and notes to prepare for exams and study successfully. Our store offers a wide selection of materials on various subjects and difficulty levels, created by experienced teachers and checked for quality. Our quality sheets are an easy and quick way to remember key points and definitions. And our study materials, tests, and quizzes will help you absorb the material and prepare for exams. Our store also has notes and lecture summaries that will help you save time and make the learning process more efficient.

Read more Read less
3.9

143 reviews

5
74
4
25
3
21
2
1
1
22

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions