During an operational test of a foam water sprinkler system, if the nozzles are plugged what color tag is used? Red Steel water storage tanks without corrosive protection are to be inspected how often? 3 years A sprinkler head with a white frame has a temperature rating of? 175 - 225 F The weekly test of an electric fire pump is how long? 10 minutes The weekly test of a Diesel fire pump is how long? 30 minutes Upon inspection of a sprinkler system, if the hydraulic nameplate is missing what color tag is used? Yellow When inspecting a preaction system, if the electrical components are not in service what color tag is used? Red Vane type water flow devices shall be tested how often? Semi-annually