MODULE 11-RESIDENTIAL ELECTRICAL SERVICES EXAM QUESTIONS AND ANSWERS GRADED A+
MODULE 11-RESIDENTIAL ELECTRICAL SERVICES EXAM QUESTIONS AND ANSWERS GRADED A+ MODULE 11-RESIDENTIAL ELECTRICAL SERVICES EXAM QUESTIONS AND ANSWERS GRADED A+ Module 11 - Residential Electrical Services A small residence has a floor area of 900 square feet. What is its general lighting load? 2,700VA Per NEC Table 220.54, a household with two dryers has a demand factor of __________. 100% If a dwelling has two kitchen areas, then the total small appliance branch circuits required would be __________. four at 1,500VA each A lighting load of 2,700VA at 120V has an amperage of __________. 22.5A When used as a grounding electrode, a ground ring must be at least __________. 20' (6.0 m) long