California Water Distribution Grade 3 Study Guide Questions and Answers with Certified Solutions | Verified | Latest Update 2024
California Water Distribution Grade 3 Study Guide Questions and Answers with Certified Solutions | Verified | Latest Update 2024 R.P.P.A. Reduced pressure principal assembly. Backflow prevention for back siphonage and back pressure. American Public Works Association color codes. White,pink,red,yellow,orange, blue, purple and green White=proposed excavation Pink=temporary survey markings red=electric power yellow=gas,oil and steam orange=communications(phone/cable) blue=water purple=reclaimed water green=sewer and storm drains. Distance between water and sewer lines. Running parallel-at least 10ft apart. Perpendicular crossing-water lines at least 1ft above sewer. Common trench-water and sewer must not be in same trench. Water main and force main regulations. Parallel-at least 10ft apart. Perpendicular crossing-Water lines at least 1ft above and force main should be encased 10ft in both directions. New water lines installed over force mains should be rated to 200psi or equivalent.
Document information
- Uploaded on
- April 10, 2024
- Number of pages
- 21
- Written in
- 2023/2024
- Type
- Exam (elaborations)
- Contains
- Questions & answers