TFM 12 Fire Alarm Technical Exam
Containing 91 Questions with Certified
Solutions Updated 2024-2025.
Does a fire hood system and a kitchen need to be monitored by the fire alarm
system? - Answer: Yes
What does P.L.F.A stand for? - Answer: Power Limited Fire Alarm
, TFM 12 Fire Alarm Technical
What does N.P.L.F.A stand for? - Answer: Non-Power Limited Fire Alarm
What is the difference between P.F.L.A and N.P.F.L.A? - Answer: an N.P.L.F.A can
operate at up to 600v, and the power output isn't limited
a P.L.F.A has the voltage and power limited by a listed power source.
What material must N.P.F.L.A circuit conductors be made from? - Answer: ONLY
solid stranded copper is permitted.
What does A.W.G stand for? - Answer: American Wire Gauge
What size conductors are permitted? - Answer: Size 18 A.W.G and 16 A.W.G are
permitted, provided they do not exceed certain capacities.
What is used to protect transformers or other devices supplied from power-supply
conductors? - Answer: An over-current device not rated over 20 amperes.
When located within 7 feet of the floor, how shall cables be fastened? - Answer:
Cables shall be fastened in an approved manner at intervals of not more than 18
inches.
Single conductors shall not be smaller than ___ A.W.G? - Answer: 18
, TFM 12 Fire Alarm Technical
Conductors of 28 A.W.G shall only be permitted in which circumstance? - Answer:
Spliced with a connector listed as suitable for 26 to 24 A.W.G
How shall P.F.L.A conductors NOT be installed? - Answer: P.F.L.A conductors shall
not be strapped, taped, or attached to the exterior of any conduit or raceway.
What is Plenum cable? - Answer: Cable that can be installed in ducts, plenums, or
other spaces used for environmental air.
What is a Riser cable? - Answer: Cable to be used in vertical wire runs in shafts
between floors. Not to be used where Plenum cable is required.
It is capable of preventing fire from rising from floor to floor.
What is general purpose cable? - Answer: Cable for general purpose fire alarm
use. Not to be used where plenum cable or riser cable is required.
It is resistant to the spread of fire.
Why 'type' shall plenum cable be? What substitutions are allowed? - Answer:
Power Limited Fire Alarm Plenum (F.P.L.P) C.M.P can be substituted.
Why 'type' shall riser cable be? What substitutions are allowed? - Answer: Power
Limited Fire Alarm Riser (F.P.L.R) C.M.P, F.P.L.P.