An area adjacent to a Division 1 location into which volatile gases might occasionally flow should be designated ___. - correct answer -Division 2 A grinding area would most likely be designated as ___. - correct answer -Class II, Division 1 A cotton textile mill would most likely be designated as ___. - correct answer -Class III A Class II atmosphere containing charcoal or coal dust would most likely be designated as ___. - correct answer -Group F Which of the following is true with regard to ignition? - correct answer -Volatile vapors will not cause ignition if diluted below the lower explosion limit. Explosion-proof equipment is rated by both classification and ___. - correct answer -temperature How many classification(s) of hazardous atmospheres are listed in the NEC? - correct answer -Three How many division(s) are there for each hazardous atmosphere classification? - correct answer -Two How many group(s) are listed under Class I, Division I? - correct answer -Four Which of the following are the groups listed under Class II, Division 1? - correct answer -E,F,G When installing circuit breakers in Class II, Division 1 hazardous locations, a ___. - correct answer -dust/ignition-proof enclosure must be used When rigid metal con