EPA 608 (TYPE II) Exam questions with correct answers
When a new system has been assembled, the first thing to do is? ans Pressurize the system with an inert gas & leak check. After installation of a field-piped R-410A split heat pulp, the unit should first be? ans Pressurized with nitrogen then leak checked. The EPA regulations require that any appliances containing more than 50 pounds of refrigerant (except for commercial & industrial process refrigeration) must be repaired when the leak rate exceeds _________ of the charge per year? ans 15% R-410A requires recovery tanks rated for at least? ans 400 psig After refrigerant liquid has been recovered from a system, any remaining vapor is? ans Condensed by the recovery system. Your recovery/recycling machine has R-502 refrigerant in it. You now have to recover refrigerant from a unit with R-22. What must be done before the R-22 refrigerant can be recovered/recycled? ans Recover as much R-502 from the recovery unit as possible, change filter, & evacuate. In a refrigeration system with a TXV (or other type of throttling device), the component directly following the condenser is the? ans Receiver