A system that provides 1 1/2 inch hose stations to supply water
for use primarily
by trained personnel or by the fire department during
initial response is a
___________. - ANSWER-Class II
Standpipe
REfrence NFPA 14 2016 Section 3.3.19.2.
Which of the following statements is incorrect when describing
a deluge system? - ANSWER-Deluge system detection devices
should be automatically supervised. Deluge systems are
required to be automatically supervised.
Reference NFPA 13 2016, Sections 3.4.4, 7.3.3.1 and 7.3.3.2.
Choose all that apply to a Dry Pipe System - ANSWER-1.
Require approved
pressure gauges on the water side of the dry
pipe valve.
,2. Permit Horizontal sidewall sprinklers to be installed so
that water is not
trapped.
3. Shall protect the dry pipe valve and supply pipe from
freezing and
mechanical
damage.
Reference NFPA 13 2016, Sections 7.2.1, 7.2.2 and 7.2.5.1.
This pump is characterized by a method of producing flow by
capturing a specific volume of fluid per pump revolution and
reducing the fluid void by a mechanical means to displace the
pumping fluid: - ANSWER-Positive
Discplacement Pump
Refrence NFPA 20 2016 Section 3.3.44.14.
Which of the following sprinklers produces large water droplets
and is listed for
its capability to provide fire control of specific high-
challenge fire hazards? -
ANSWER-CMSA
Sprinkler
Refrence 13
2016
Section
3.6.4.2.
,A standpipe system with no permanently attached water supply
that relies exclusively on the fire department connection to
supply the system demand. - ANSWER-Manual Dry
Reference NFPA 14
2016
Section
3.3.17.4.
For corrosive water conditions, steel pipe on the suction side
of the pump is
required to be: - ANSWER-Galvanized or painted on the
interior with a paint
recommended for submerged
surfaces
Refrence NFPA 20
2016
Section
4.14.1.2.
The distance between the bottom of the strainer and the bottom
of the wet pit on a vertical shaft turbine pump should be: -
ANSWER-One half of the pump bowl diameter but not less than
12 inches.
Reference NFPA 20 2016, Figure A.7.2.2.1 (see note in figure)
, Determine the max allowable shutoff pressure for a fire
pump with a rated
cpacity of 750 gpm and a rated head of 60 ft. -
ANSWER-36 psi.
1.4 x 60 ft = 84 ft,
Head = P psi/0.433,
P = Head x 0.433, P = 84 x 0.433 = 36.37 psi.
This complex phenomenon specific to pumps or other
hydraulic equipment is the result of suction pressure falling
below vapor pressure corresponding to the water temperature:
- ANSWER-Cavitation
A high-rise building where the floor of an occupiable story is
greater than _____
above the lowest level of fire department vehicle access. -
ANSWER-75ft
Refrence NFPA 14
2016
Section
3.3.7.
In a manufacturing plant classified as Ordinary Hazard Group
2, the sprinkler