Question: Manual actuators shall not have a force more than.
Correct Answer:
40lbs
Question: Manual actuators shall not have a movement of more than.
Correct Answer:
14 inches
Question: Instructions with pictographs and lettering shall be atleast.
Correct Answer:
1/4 inches
Question: Pipe and fittings shall be made of.
Correct Answer:
Non combustible materials
Question: galvanized pipe and fittings.
Correct Answer:
Shall not be used
Question: During assembly examine pipe.
Correct Answer:
Internally to detect and remove contaminants
Question: Readily acces means for manual actuators.
Correct Answer:
Shall be located in a path of egress
, Question: Manual actuators shall be installed.
Correct Answer:
No more than 48in and no less than 42in
Question: Fusible links shall be located.
Correct Answer:
At above each cooking appliance
Question: Fusible links shall be.
Correct Answer:
12 in in front of said item
Question: A test shall be used on pipe using.
Correct Answer:
Nitrogen or dry air not exceeding normal operating pressure
Question: Piping shall not.
Correct Answer:
Be hydrostatic tested
Question: Owners inspection.
Correct Answer:
Monthly
Question: Owners inspection records shall be retained.
Correct Answer:
Semi-annualy
Question: Wet chemical fire extinguisher service at.
Correct Answer:
Every 6 months