FLORIDA Burglar Alarm License EXAM STUDY GUIDE 2026/2027 ACCURATE QUESTIONS WITH CORRECT DETAILED SOLUTIONS || 100% GUARANTEED PASS NEWEST VERSION 1. FASA - ANSWER Fire Alarm System Agent 2. BASA - ANSWER Burglar Alarm System Agent 3. Florida Statute 489, Part II - ANSWER Regulates alarm system contracting in Florida 4. Minimum age for FASA/BASA license - ANSWER 18 years old 5. DBPR - ANSWER Department of Business and Professional Regulation 6. Purpose of the DBPR - ANSWER To license and regulate professionals and businesses in Florida 7. Validity of FASA/BASA ID - ANSWER 2 years 8. Requirements before working on an alarm system - ANSWER Required training and a background check 9. Legal work on alarm systems in Florida - ANSWER False 10. Penalty for working without proper licensing in Florida - ANSWER It can result in fines, license suspension, or criminal charges 11. Two main types of alarm systems - ANSWER Fire and Burglar 12. Primary function of a fire alarm system - ANSWER To detect and alert occupants of fire or smoke 13. Main purpose of a burglar alarm system - ANSWER To detect unauthorized entry and alert occupants or authorities 14. Control panel in an alarm system - ANSWER Manages system signals and communication between devices 15. Common type of sensor used in burglar alarms - ANSWER Motion detector 16. Common sensor in fire alarm systems - ANSWER Smoke detector 17. Component that alerts during an alarm event - ANSWER Audible/visual notification devices (e.g. sirens, strobes) 18. Purpose of a backup battery in an alarm system - ANSWER To keep the system functioning during a power outage 19. Connection of all alarm systems to a central monitoring station - ANSWER False 20. AHJ - ANSWER Authority Having Jurisdiction 21. CFPS - ANSWER Certified Fire Protection Specialist 22. FACU - ANSWER Fire Alarm Control Unit (also called a Fire Alarm Control Panel (FACP)) 23. FAS - ANSWER Fire Alarm System 24. IBC - ANSWER International Building Code 25. IDC - ANSWER Initiating Device Circuit 26. IFC - ANSWER International Fire Code 27. NAC - ANSWER Notification Appliance Circuit 28. NEC - ANSWER National Electrical Code 29. NFPA - ANSWER National Fire Protection Association 30. NICET - ANSWER National Institute for Certification in Engineering Technologies 31. SLC - ANSWER Signaling Line Circuit 32. Addressable Fire Alarm System - ANSWER A system in which the fire alarm control unit and its associated devices are connected and communicate digitally. Each device is separately addressed. 33. Alarm Signal - ANSWER A signal that results from the manual or automatic detection of an alarm condition. (NFPA 72 2016, Section 3.3.253.1) 34. Authority Having Jurisdiction (AHJ) - ANSWER An organization, office, or individual responsible for enforcing requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure. (NFPA 72 2016, Section 3.2.2) 35. Beam Construction - ANSWER Ceilings that have solid structural or solid nonstructural members projecting down from the ceiling surface more than 4 in. (100 mm) and spaced more than 36 in. (910 mm), center to center. (NFPA 72 2016, Section 3.3.38.1) 36. Which of the following is NOT an approved method of mounting a smoke detector in a duct? - ANSWER The correct answer is: Cutting a hole in the duct and outside rigid mounting. This is not one of the four approved methods per NFPA 72 2016, Section 17.7.5.5.2. 37. A smoke detector installed in an air duct system is permitted to be used as a substitute for open area protection. - ANSWER The correct answer is: False per NFPA 72 2016, Sections 17.7.4.3 and 17.7.5.2.1. 38. Smoke detectors installed in air duct systems are normally used to control spreading smoke. - ANSWER The correct answer is: True per NFPA 72 2016, Section 17.7.5.1(2). 39. Spot type heat detectors are not required to be spaced closer than ____ times the ____. - ANSWER The correct answer is: 0.4 and ceiling height per NFPA 72 2016, Section 17.6.3.5.2. 40. When installing a smoke detector for door release service and the depth of the wall above the door is greater than 24 inches on one side only, we must install _____ ceiling-mounted detector(s) on the higher side or ____ wall mounted detector(s) (one on each side of the doorway). - ANSWER The correct answer is: 1, 2 per NFPA 72 2016, Section 17.7.5.6.5.1(B) and Figure 17.7.5.6.5.1(A). 41. What is the maximum permitted spacing between two heat detectors when the detectors have a listed spacing of 50 ft. and the ceiling height the detectors will be mounted on has a height of 28 ft, 4 inches? - ANSWER The correct answer is: 17 ft. per NFPA 72 2016, Table 17.6.3.5.1. Using Table 17.6.3.5.1 we see that a ceiling height above 28 ft. and up to and including 30 ft., we must multiply the detector's listed spacing by 0.34. 50- ft. spacing x 0.34 = 17 ft. 42. For an irregularly shaped area, what is the maximum permitted distance a heat detector may be from the farthest point of a sidewall or corner within its zone of protection when the ceiling height is 10 ft. and the detector's listed spacing is 40 ft? - ANSWER The correct answer is: 28 ft. per NFPA 72 2016, Section 17.6.3.1.2. The farthest point to a sidewall or corner to the detectors is 0.7 x the listed spacing. In this case, the ceiling height is 10 ft. or less so we do not have to reduce heat detector spacing due to ceiling height. The listed spacing is 40 ft. x 0.7 which equals 28 ft. 43. For a ceiling height of 16 ft, we must multiply a heat detector's listed spacing by what factor? - ANSWER The correct answer is: 0.77 per

Show more Read less
Institution
FLORIDA Burglar Alarm License
Course
FLORIDA Burglar Alarm License

Content preview

FLORIDA Burglar Alarm License EXAM
STUDY GUIDE 2026/2027 ACCURATE
QUESTIONS WITH CORRECT
DETAILED SOLUTIONS ||
100% GUARANTEED PASS
<NEWEST VERSION>


1. FASA - ANSWER ✔ Fire Alarm System Agent

2. BASA - ANSWER ✔ Burglar Alarm System Agent

3. Florida Statute 489, Part II - ANSWER ✔ Regulates alarm system
contracting in Florida

4. Minimum age for FASA/BASA license - ANSWER ✔ 18 years old

5. DBPR - ANSWER ✔ Department of Business and Professional Regulation

6. Purpose of the DBPR - ANSWER ✔ To license and regulate professionals
and businesses in Florida

7. Validity of FASA/BASA ID - ANSWER ✔ 2 years

8. Requirements before working on an alarm system - ANSWER ✔ Required
training and a background check

9. Legal work on alarm systems in Florida - ANSWER ✔ False

10.Penalty for working without proper licensing in Florida - ANSWER ✔ It
can result in fines, license suspension, or criminal charges

,11.Two main types of alarm systems - ANSWER ✔ Fire and Burglar

12.Primary function of a fire alarm system - ANSWER ✔ To detect and alert
occupants of fire or smoke

13.Main purpose of a burglar alarm system - ANSWER ✔ To detect
unauthorized entry and alert occupants or authorities

14.Control panel in an alarm system - ANSWER ✔ Manages system signals
and communication between devices

15.Common type of sensor used in burglar alarms - ANSWER ✔ Motion
detector

16.Common sensor in fire alarm systems - ANSWER ✔ Smoke detector

17.Component that alerts during an alarm event - ANSWER ✔ Audible/visual
notification devices (e.g. sirens, strobes)

18.Purpose of a backup battery in an alarm system - ANSWER ✔ To keep the
system functioning during a power outage

19.Connection of all alarm systems to a central monitoring station - ANSWER
✔ False

20.AHJ - ANSWER ✔ Authority Having Jurisdiction

21.CFPS - ANSWER ✔ Certified Fire Protection Specialist

22.FACU - ANSWER ✔ Fire Alarm Control Unit (also called a Fire Alarm
Control Panel (FACP))

23.FAS - ANSWER ✔ Fire Alarm System

24.IBC - ANSWER ✔ International Building Code

,25.IDC - ANSWER ✔ Initiating Device Circuit

26.IFC - ANSWER ✔ International Fire Code

27.NAC - ANSWER ✔ Notification Appliance Circuit

28.NEC - ANSWER ✔ National Electrical Code

29.NFPA - ANSWER ✔ National Fire Protection Association

30.NICET - ANSWER ✔ National Institute for Certification in Engineering
Technologies

31.SLC - ANSWER ✔ Signaling Line Circuit

32.Addressable Fire Alarm System - ANSWER ✔ A system in which the fire
alarm control unit and its associated devices are connected and communicate
digitally. Each device is separately addressed.

33.Alarm Signal - ANSWER ✔ A signal that results from the manual or
automatic detection of an alarm condition. (NFPA 72 2016, Section
3.3.253.1)

34.Authority Having Jurisdiction (AHJ) - ANSWER ✔ An organization,
office, or individual responsible for enforcing requirements of a code or
standard, or for approving equipment, materials, an installation, or a
procedure. (NFPA 72 2016, Section 3.2.2)

35.Beam Construction - ANSWER ✔ Ceilings that have solid structural or
solid nonstructural members projecting down from the ceiling surface more
than 4 in. (100 mm) and spaced more than 36 in. (910 mm), center to center.
(NFPA 72 2016, Section 3.3.38.1)

36.Which of the following is NOT an approved method of mounting a smoke
detector in a duct? - ANSWER ✔ The correct answer is: Cutting a hole in
the duct and outside rigid mounting. This is not one of the four approved
methods per NFPA 72 2016, Section 17.7.5.5.2.

, 37.A smoke detector installed in an air duct system is permitted to be used as a
substitute for open area protection. - ANSWER ✔ The correct answer is:
False per NFPA 72 2016, Sections 17.7.4.3 and 17.7.5.2.1.

38.Smoke detectors installed in air duct systems are normally used to control
spreading smoke. - ANSWER ✔ The correct answer is: True per NFPA 72
2016, Section 17.7.5.1(2).

39.Spot type heat detectors are not required to be spaced closer than ____ times
the ____. - ANSWER ✔ The correct answer is: 0.4 and ceiling height per
NFPA 72 2016, Section 17.6.3.5.2.

40.When installing a smoke detector for door release service and the depth of
the wall above the door is greater than 24 inches on one side only, we must
install _____ ceiling-mounted detector(s) on the higher side or ____ wall-
mounted detector(s) (one on each side of the doorway). - ANSWER ✔ The
correct answer is: 1, 2 per NFPA 72 2016, Section 17.7.5.6.5.1(B) and
Figure 17.7.5.6.5.1(A).

41.What is the maximum permitted spacing between two heat detectors when
the detectors have a listed spacing of 50 ft. and the ceiling height the
detectors will be mounted on has a height of 28 ft, 4 inches? - ANSWER ✔
The correct answer is: 17 ft. per NFPA 72 2016, Table 17.6.3.5.1. Using
Table 17.6.3.5.1 we see that a ceiling height above 28 ft. and up to and
including 30 ft., we must multiply the detector's listed spacing by 0.34. 50-
ft. spacing x 0.34 = 17 ft.

42.For an irregularly shaped area, what is the maximum permitted distance a
heat detector may be from the farthest point of a sidewall or corner within its
zone of protection when the ceiling height is 10 ft. and the detector's listed
spacing is 40 ft? - ANSWER ✔ The correct answer is: 28 ft. per NFPA 72
2016, Section 17.6.3.1.2. The farthest point to a sidewall or corner to the
detectors is 0.7 x the listed spacing. In this case, the ceiling height is 10 ft. or
less so we do not have to reduce heat detector spacing due to ceiling height.
The listed spacing is 40 ft. x 0.7 which equals 28 ft.

43.For a ceiling height of 16 ft, we must multiply a heat detector's listed
spacing by what factor? - ANSWER ✔ The correct answer is: 0.77 per

Written for

Institution
FLORIDA Burglar Alarm License
Course
FLORIDA Burglar Alarm License

Document information

Uploaded on
June 7, 2026
Number of pages
34
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

$14.99
Get access to the full document:

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
ProfBenjamin Havard School
View profile
Follow You need to be logged in order to follow users or courses
Sold
701
Member since
1 year
Number of followers
17
Documents
3932
Last sold
7 hours ago
EXCELLENT ACHIEVERS LIBRARY

As a professional tutor, I provide exceptional assistance with homework, quizzes, and exams across various subjects, including Psychology, Nursing, Biological Sciences, Business, Engineering, Human Resource Management, and Mathematics. I am dedicated to offering high-quality support and ensuring that all work meets scholarly standards. To enhance the effectiveness of our services, I work with a team of experienced tutors to create comprehensive and effective revision materials. Together, we are committed to helping students achieve excellent grades through our collaborative efforts and expertise.

Read more Read less
3.8

143 reviews

5
62
4
20
3
37
2
12
1
12

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions