Which of the following would not require secondary containment testing?
a.) Interstitial space hydrostatically monitored
b.) Under-dispenser containment
c.) Turbine piping sump
d.) Secondary piping -- ANSWER--a.) Interstitial space hydrostatically monitored
CCR Title 23, Sec 2637(g)
Fiberglass tanks shall be repaired by the following, except:
a.) Small fractures and fissures may be repaired with epoxy
b.) Fiberglass cloth with a minimum dimension 12 x 12 inches centered over the area to be
repaired.
c.) A second layer of fiberglass cloth shall be installed directly over the primary cloth layer
and shall be cut to overlap the primary patch by 5 inches on all sides.
d.) The repaired tank shall be tested for tightness within 30 calendar days following the date
of the completion of the repair. -- ANSWER--c.) A second layer of fiberglass cloth shall be
installed directly over the primary cloth layer and shall be cut to overlap the primary patch by
5 inches on all sides.
CCR Title 23, Sec 2661(d)(4)
, 2
Automatic line leak detectors shall be installed on underground pressurized piping and shall
be capable of detecting a 3-gallon per hour leak rate at 10 psi within 1 hour with a probability
of detection of at least % and a probability of false alarm no greater than %.
a.) 95, 5
b.) 98, 2
c.) 5, 95
d.) 2, 98 -- ANSWER--a.) 95, 5
CCR Title 23, Sec 2636(f)(2) & 2643(c)(1)
An emergency impact valve (shear valve) is found in the following location on an UST
System.
a.) At the turbine piping termination
b.) Base of the dispenser
c.) Under the extractor tee
d.) Spill container -- ANSWER--b.) Base of the dispenser
Notification to perform a secondary containment test must be given to the local agency by:
a.) A service technician or a licensed tank tester.
b.) Cathodic protection tester.
c.) Owner/operator of UST.
d.) State Water Resources Control Board. -- ANSWER--c.) Owner/operator of UST
CCR Title 23, Sec 2637(f)
An owner or operator of an underground storage tank or any part thereof that is destined for a
specific reuse shall advise the local agency, within the time frame specified by that agency, of
all of the following, except:
, 3
a.) The nature of intended use
b.) The name of the new owner and new operator of the UST
c.) The location of intended use
d.) The State Water Resources Control Board must be advised not the local agency --
ANSWER--d.) The State Water Resources Control Board must be advised not the local
agency
CCR Title 23, Sec 2672(b)(4)
Any person(s) installing underground storage tank systems or components shall be certified
or licensed by:
a.) The Contractors State License Board
b.) The local agency
c.) The State Water Resources Control Board
d.) The Regional Water Quality Board -- ANSWER--a.) The Contractors State License Board
CCR Title 23, Sec 2715(g)
The designated UST operator(s) shall perform monthly visual inspections of all UST's for
which they are designated. The monthly visual inspection shall include all of the following,
except:
a.) Inspecting for the presence of hazardous substances, water, or debris in spill containers.
b.) By July 1, 2005, verify that all facility employees have been trained.
c.) Reviewing the alarm history report or log for the previous month.
d.) Inspecting for the presence of hazardous substances, water, or debris in containment
sumps regardless of documentation showing each alarm for the previous month has been
responded to appropriately. -- ANSWER--d.) Inspecting for the presence of hazardous
substances, water, or debris in containment sumps regardless of documentation showing each
alarm for the previous month has been responded to appropriately.
, 4
CCR xTitle x23, xSec x2715(c)
Which xagency xapproves xa xsite-specific xvariance xwhich xallows xfor xan xalternative xmethod xof
x construction xor xmonitoring:
a.) The xRegional xWater xQuality xBoard
b.) The xState xWater xResources xControl xBoard
c.) The xDepartment xof xToxic xSubstance xControl
d.) The xlocal xagency x-- xANSWER--a.) xThe xRegional xWater xQuality
Board xCCR xTitle x23, xSec x2681(a)
x
The xregulations xto xenforce xcompliance xof xunderground xstorage xtank xsystems xin xthe xstate xare
x found xin?
a.) Code xof xFederal xRegulations, x40 xCFR xPart x281
b.) California xCode xof xRegulations, xTitle x23, xChapter x16
c.) Code xof xFederal xRegulations, x40 xCFR xPart x280
d.) California xCode xof xRegulations, xTitle x23, xChapter x17 x-- xANSWER--b.) xCalifornia xCode
of xRegulations; xTitle x23, xChapter x16
x
By xdefinition xan x"underground xstorage xtank xsystem" xincludes
a.) The xtank, xall xconnected xpiping xand xdispensers
b.) The xtank, xall xconnected xpiping, xancillary xequipment xand xcontainment xsystem
c.) Only xthe xtank
d.) Only xtanks xtotally xbeneath xthe xsurface xof xthe xground x-- xANSWER--b.) xThe xtank,
all xconnected xpiping, xancillary xequipment xand xcontainment xsystem